Step 6. Echo-Curve
Verification with Empty
Tank
When the tank or chamber is empty, download and review the echo-curve
according to the following steps:
1. Compare echo-curve with previous plots
Compare the echo-curve with previous plots, taken during
commissioning. There should be no major differences. Especially make
sure to review:
• the amplitude and position of the reference pulse
• if all noise is below the threshold
2. Store the echo-curve
Permanently store the echo-curve for future use, with re-occurring
verification procedures. Ensure that the reference echo is visible in the
plot.
Step 7. Monitor Level
while Filling
Repeat Step 5, but fill the tank or chamber instead of emptying it.
Step 8. Archive Files Save Echo Curve and Config File
Permanently store the echo-curve and configuration back-up files for future
use, with re-occurring verification procedures.
In Rosemount Radar Master:
Rosemount Radar Master > Device > Backup Config to file
Rosemount Radar Master > Tools > Echo Curve > Record