Reference Manual
00809-0600-4026, Rev BA
December 2011
6-7
Rosemount Process Radar
Step 3. Verification Viewing Measurement Data
In Rosemount Radar Master
Rosemount Radar Master > Tools > Device Display
Figure 6-6. Presentation of
measurement data in RRM
Figure 6-7. Presentation of
Analog Output value in RRM
For more information, see the Rosemount 5400 Series Reference Manual
(Document No. 00809-0100-4026) section “Viewing Measurement Data”.
Viewing Measurement Data in AMS Suite
Verify Analog Output (HART devices only)
Ensure that the loop has been set to manual mode in the DCS for the
applicable transmitter.
Use the transmitter's built-in simulation mode to verify the analog output
settings. Output at least one arbitrary level or interface and verify that the
readings in the DCS match up.