Reference Manual
00809-0600-4026, Rev BA
December 2011
3-3
Rosemount Process Radar
Figure 3-2. Example of Range
Value settings (HART)
For more information, see the Rosemount 5300 Series Reference
Manual (Document No. 00809-0100-4530) section “Basic
Configuration Parameters”.
•AI Block (F
OUNDATION Fieldbus)
A minimum of four parameters are required to configure the AI Block:
1. Channel - Corresponds to the desired sensor measurement
2. L_TYPE - Defines the relationship to the desired output of the AI
Block. Direct or indirect root.
3. XD_SCALE - Include 0%, 100%, and engineering units.
4. OUT_SCALE - Include 0%, 100%, and engineering units.
For more information, see the Rosemount 5300 Series Reference Manual
(Document No. 00809-0100-4530) section “F
OUNDATION Fieldbus Overview”.
Basic Configuration Using Rosemount Radar Master
1. Start the Guided Setup
2. Start the Configuration Wizard
3. Click the Device specific setup button
This will show if any additional configuration is needed.
4. Restart the transmitter
5. View live values from the device
6. Backup
For more information, see the Rosemount 5300 Series Reference Manual
(Document No. 00809-0100-4530) section “Basic Configuration Using
Rosemount Radar Master”.
20 mA Upper Range Value (URV) = 100%
Upper Transition Zone
Product Level
Lower Transition Zone
4 mA Lower
Range Value
(LRV) = 0%
Upper Reference Point
Range 0-100%
Lower Reference Point (Level=0)