Reference Manual
00809-0600-4026, Rev BA
December 2011
Rosemount Process Radar
2-6
Step 2. Connect The
Wiring
It is recommended that shielded twisted pair wiring (18-12 AWG) suitable for
the supply voltage be used and, if applicable, approved for use in hazardous
areas. For electrical information, such as power supply, see diagrams and
drawings for HART, Modbus, and F
OUNDATION fieldbus on the following
pages.
To Connect the
Transmitter
1. Make sure the housing is grounded (including IS ground inside Terminal
compartment) according to Hazardous Locations Certifications, national
and local electrical codes.
2. Verify that the power supply is disconnected.
3. Remove the terminal block cover (see picture below).
4. Pull the cable through the cable gland/conduit. For Explosion-proof /
Flameproof installations, only use cable glands or conduit entry devices
certified Explosion-proof or Flameproof. Install wiring with a drip loop
where the bottom of the loop must be lower than the cable/conduit entry.
5. To connect the wires, see the illustrations on the following pages.
6. Use the enclosed metal plug to seal any unused port.
7. Tighten the cable gland.
8. Mount the cover and make sure it is fully engaged to meet
Explosion-proof requirements (adapters are required if M20 glands are
used).
For ATEX, IECEx, NEPSI, INMETRO, and TIIS installations, lock the
cover with the locking screw.
9. Connect the power supply.
NOTE
Use PTFE tape or other sealant at the NPT threads in the Cable Entries.
Terminal Block
Cable Entry, ½ in.
NPT - 14 or
M20x1.5 adapter
Internal
Ground Screw
Terminals for
signal and
power supply
External Ground
Screw
Terminal
Block
Cover
Cable Entry,
½ in. NPT - 14
or M20x1.5
adapter
Remove the orange,
protective, plastic plugs, used
for transportation.
Seal any unused port with the
enclosed metal plug.
Locking screw