Rosemount Process Radar
Special Tools
Not required.
Product Repair
All failures detected by the transmitter diagnostics or by the proof test must be
reported. Feedback can be submitted electronically at
www.emersonprocess.com/rosemount/safety (Contact Us).
The 5300 is repairable by major component replacement. Additional
information is available in the Rosemount 5300 Series Reference Manual
(Document No. 00809-0100-4530).
References Specifications
The Rosemount 5300 must be operated in accordance with the functional and
performance specifications provided in the Rosemount 5300 Series
Reference Manual (Document No. 00809-0100-4530), Appendix A:
Reference Data.
Failure Rate Data
The FMEDA report includes failure rates and common cause Beta factor
estimates. The full report is accessible at
www.emersonprocess.com/rosemount/safety/PriorUse.htm.
Useful Lifetime
The established failure rates of electrical components apply within the useful
lifetime, which should be based on experience. According to IEC 61508-2,
7.4.7.4, note 3, the useful lifetime often lies within a range of 8 to 12 years.