Section 2 • Operational Descriptions
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Figure 2-6. Control Panel Master Power and Emergency Stop Electrical Circuit
OIL HEATERS
Immersion Heaters in the oil separator are controlled by
the compressor PLC to maintain warm oil. The heaters
cycle on and off to maintain a desired separator oil tem-
perature range.
SUCTION OIL INJECTION SOLENOID
Used on 401mm screw machines (models 2401-3001).
If installed, the suction oil injection solenoid feeds addi-
tional oil from the oil separator to compressor suction
on start. The valve is opened for a settable time after the
compressor main motor starts.
SUCTION-DISCHARGE EQUALIZING SOLENOID
If installed, the equalizing solenoid opens for a settable
time on compressor stop to equalize pressure between
suction and discharge of the compressor.
OIL DRAIN SOLENOID
If installed, the oil drain solenoid valve opens for a set-
table time on compressor stop to allow oil to drain from
the compressor. It also opens during the prelube retry
wait periods in the prelube sequence.