11 – 10
Section 11 • Alarms, Trips, Status Information & Troubleshooting
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Trip Message Cause(s) Notes
(T015) Trip: Low Oil Injection
Temperature
Oil Injection Temperature is Below
"Oil Injection Temperature" Low Trip
Setpoint after compressor has com-
pleted pre-lube and warm up stages.
(T016) Trip: High Oil Injection
Temperature
Oil Injection Temperature exceeds
"Oil Injection Temperature" High Trip
Setpoint
(T017) Trip: Low Process
Temperature
Process Temperature falls below
Process Temperature Low Trip
Setpoint in Process Temperature
control or if displaying Process
Temperature.
Active if controlling or displaying
Process Temperature
(T018) Trip: (Unassigned)
(T019) Trip: (Unassigned)
(T020) Trip: Low Liquid Refrigerant
Temperature
Liquid Refrigerant Temperature
falls below Liquid Refrigerant
Temperature Low Trip Setpoint
if displaying Liquid Refrigerant
Temperature
Active if displaying Liquid Refrigerant
Temperature
(T021) Trip: Low Suction Pressure
Stpt. 1
Setpoint 1 is selected and Suction
Pressure falls below Suction Pressure
Low Trip Setpoint.
(T022) Trip: Low Suction Pressure
Stpt. 2
Setpoint 2 is selected and Suction
Pressure falls below Suction Pressure
Low Trip Setpoint.
(T023) Trip: High Discharge Pressure
Stpt. 1
Setpoint 1 is selected and Discharge
Pressure falls below Discharge
Pressure High Trip Setpoint.
(T024) Trip: High Discharge Pressure
Stpt. 2
Setpoint 2 is selected and Discharge
Pressure falls below Discharge
Pressure High Trip Setpoint.
(T025) Trip: Low Net Oil Pressure
- Run
Net Oil Pressure (Oil Manifold
Pressure - Suction Pressure) falls
below Net Oil Pressure Low Trip
Setpoint after prelube and warmup
are complete.
(T026) Trip: Failed To Reach Prelube
Pressure - Start Sequence Aborted
Failed to maintain required prelube
pressure for required time during
start-up.
(T027) Trip: High Oil Filter
Differential - Start
Oil Filter Differential (Filter In
Pressure - Oil Manifold Pressure)
exceeds Oil Filter Differential - Start
High Trip Setpoint when compres-
sor is running and before Oil Filter
Differential Start-Run Changeover
Timer expires.