2 – 4
Section 2 • Operational Descriptions
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
AUTO START-STOP
When enabled, the Auto Start-Stop feature will allow
the compressor to cycle on and off based on the con-
trolled pressure or temperature. The Anti-Recycle timer
still applies when Auto Start-Stop is enabled. Additional
variables that factor in to Auto Start-Stop are described
below:
Auto Start Pressure/Temperature: Pressure or
Temperature at which the control will start the
compressor.
Auto Start Delay: Amount of time that the Auto Start
Pressure/Temperature must be met before the com-
pressor is commanded to start.
Auto Stop Pressure/Temperature: Pressure or
Temperature at which the control will stop the
compressor.
Auto Stop Delay: Amount of time that the Auto Stop
Pressure/Temperature must be met with the capac-
ity slide at or below “Minimum Slide Position” before
the compressor is commanded to stop.
Minimum Slide Position: Position the capacity slide
must be at or below before the compressor is com-
manded to stop.
When Auto Start-Stop control is enabled, it will function
as follows:
When Auto Start Pressure/Temperature is met for the
Auto Start Delay Time, the compressor will be com-
manded to start.
When the Auto Stop Pressure/Temperature is met
and the capacity slide has decreased to the Minimum
Slide Position for the Auto Stop Delay time, the com-
pressor will be commanded to stop.
ANTI-RECYCLE
After the compressor main motor stops, it is not allowed
to re-start again for a settable time. This is to protect the
compressor from damage by allowing oil to drain from it
before the next start. If the Anti-Recycle timer is active,
a banner will appear on the overview and menu screens
that shows the remaining time. If a start is initiated, the
compressor state indicator will indicate “Standby” until
the Anti-Recycle timer is done. If all other permissives
are met, the compressor will re-start.
CAPACITY SLIDE CONTROL
Reference examples, Figures 2-2, 2-3 and 2-4
While the compressor is running, the controller will au-
tomatically adjust the position of the compressor capac-
ity slide valve to hold the desired pressure or tempera-
ture. Three control methods are available:
Discharge Pressure Control: Compressor loads to in-
crease discharge Pressure to desired setpoint
Suction Pressure Control: Compressor loads to lower
suction pressure to desired setpoint
• Process Temperature Control: Compressor Loads to
lower process temp to desired setpoint. An instru-
ment to monitor the Process Temperature is required.
The capacity slide control of the PLC operates by periodi-
cally calculating an adjustment to the capacity slide po-
sition based on where the selected process variable is in
relation to the target setpoint. When the process pres-
sure or temperature is far away from the setpoint, capac-
ity slide position is adjusted by the de ned maximum.
As the control pressure or temperature gets closer to
setpoint, smaller adjustments are made to the capacity
slide position. All of the variables that factor in to this
calculation are described below:
Target pressure or Temperature – the desired suction
pressure, discharge pressure, or process temperature
that the machine will try to maintain.
Upper Proportional Deadband – Range above Target
pressure or Temperature where no capacity slide ad-
justment will be made.
Lower Proportional Deadband – Range below Target
pressure or Temperature where no capacity slide ad-
justment will be made.
Upper Proportional Band – Range above Target pres-
sure or Temperature where adjustments to capacity
slide position are made proportional to the differ-
ence between Target pressure or Temperature and
Actual. Outside this range, the adjustment made will
be the set maximum.
Lower Proportional Band - Range below Target pres-
sure or Temperature where adjustments to capacity
slide position are made proportional to the differ-
ence between Target pressure or Temperature and
Actual. Outside this range, the adjustment made will
be the set maximum.
Load Interval Time – Cycle time for calculating ca-
pacity slide position adjustment when the controller
is calling for the machine to increase capacity slide
position. Where the Load Interval Time is T1, the
control will make an adjustment calculation every T1
seconds.