Section 12 • Communications with a Central Controller/DCS
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
Alarm and Trip Data
Alarm and Trip Data is presented in Double Integer Format. To interpret the Alarm and Trip data, it is necessary to ad-
dress the speci c bits of the Double Integer.
ALARMS AND TRIPS (Data Type = DINT)
Interface Tag Description
BOOL_OUT[1].0 (A001) Alarm: (Unassigned)
BOOL_OUT[1].1 (A002) Alarm: PLC to Central Comms Faulted
BOOL_OUT[1].2 (A003) Alarm: High Main Motor Amps
BOOL_OUT[1].3 (A004) Alarm: (Unassigned)
BOOL_OUT[1].4 (A005) Alarm: (Unassigned)
BOOL_OUT[1].5 (A006) Alarm: Low Separator Oil Level
BOOL_OUT[1].6 (A007) Alarm: Not Assigned
BOOL_OUT[1].7 (A008) Alarm: Not Assigned
BOOL_OUT[1].8 (A009) Alarm: Not Assigned
BOOL_OUT[1].9 (A010) Alarm: Not Assigned
BOOL_OUT[1].10 (A011) Alarm: Low Suction Temperature
BOOL_OUT[1].11 (A012) Alarm: High Discharge Temperature
BOOL_OUT[1].12 (A013) Alarm: Low Oil Separator Temperature - Start
BOOL_OUT[1].13 (A014) Alarm: Low Oil Separator Temperature - Run
BOOL_OUT[1].14 (A015) Alarm: Low Oil Injection Temperature
BOOL_OUT[1].15 (A016) Alarm: High Oil Injection Temperature
BOOL_OUT[1].16 (A017) Alarm: Low Process Temperature
BOOL_OUT[1].17 (A018) Alarm: High Process Temperature
BOOL_OUT[1].18 (A019) Alarm: High Suction Temperature
BOOL_OUT[1].19 (A020) Alarm: Low Liquid Refrigerant Temperature
BOOL_OUT[1].20 (A021) Alarm: Low Suction Pressure Stpt. 1
BOOL_OUT[1].21 (A022) Alarm: Low Suction Pressure Stpt. 2
BOOL_OUT[1].22 (A023) Alarm: High Discharge Pressure Stpt. 1
BOOL_OUT[1].23 (A024) Alarm: High Discharge Pressure Stpt. 2
BOOL_OUT[1].24 (A025) Alarm: Low Net Oil Pressure - Run
BOOL_OUT[1].25 (A026) Alarm: Unassigned
BOOL_OUT[1].26 (A027) Alarm: High Oil Filter Differential - Start
BOOL_OUT[1].27 (A028) Alarm: High Oil Filter Differential - Run
BOOL_OUT[1].28 (A029) Alarm: Low Oil Pressure - Start
BOOL_OUT[1].29 (A030) Alarm: (Unassigned)
BOOL_OUT[1].30 (A031) Alarm: Out of Range: Oil Cooler Inlet Temp
BOOL_OUT[1].31 (A032) Alarm: Out of Range: Oil Cooler Outlet Temp
BOOL_OUT[2].0 (A033) Alarm: Out of Range: Condensing Pressure
Table 12-3. Alarm Data