Section 2 • Operational Descriptions
Single Screw Compressor PLC Operation Manual • Vilter/Emerson • 35391CM
VFD CAPCITY CONTROL
When a VFD is used on the compressor main motor to
control capacity, it works in conjunction with the ca-
pacity slide valve to maintain the Target pressure or
Temperature. At start, the compressor main motor
will run at 50% speed until the capacity slide reaches
its maximum position. At this point, the VFD will begin
adjusting the speed of the main motor to maintain the
target pressure or temperature. The speed adjustments
made by the controller follow the same algorithm as the
capacity slide. Additional variables that factor into the
operation of a main motor VFD are described below:
Max Speed Increase per Interval – Maximum mo-
tor speed adjustment that can be made when the
control is calling for the machine to increase motor
speed. Where the Maximum Speed Increase is S
1
,
the main motor will speed up by S
1
% every cycle of
the Load Interval Timer when outside the bandwidth
range. When inside the bandwidth range, the motor
speed adjustment will be a percentage of S
1
.
Max Speed Decrease per Interval – Maximum mo-
tor speed adjustment that can be made when the
control is calling for the machine to decrease motor
speed. Where the Maximum Speed Decrease is S
2
,
the main motor will slow down by S
2
% every cycle of
the Unload Interval Timer when outside the band-
width range. When inside the bandwidth range, mo-
tor speed adjustment will be a percentage of S
2
.
VOLUME SLIDE CONTROL
When the compressor is running, the volume slide valve
adjusts automatically to operating conditions for opti-
mal ef ciency. The volume slide position is determined
by a lookup table that takes into account the size and
model of compressor, type of refrigerant or gas being
compressed, capacity slide position, and pressure ratio.
An offset can be applied to the volume slide’s calculated
target position to adjust it for unique running condi-
tions. In Compressor Control Setpoints page 2, the set-
points below are available:
Volume Slide Adjustment Factor: amount of offset
that will be applied to the calculated volume slide po-
sition target.
Capacity Slide Range Adjustment Factor is Applied:
The volume slide adjustment factor or offset will be
applied when the capacity slide is within this range.
The volume slide may be manually controlled, although
it is best to leave it in Auto Mode. Manual volume slide
control may be used when calculating an offset to apply
to the volume slide calculation. The volume slide mode
is settable in the “Volume Slide Details” screen.
When the compressor is stopped, the volume slide valve
is commanded to go to its minimum position.
SAFETIES
The compressor controller continuously monitors oper-
ational and process data and annunciates an alarm and/
or stops the machine if any condition becomes abnor-
mal. Two levels of safeties exist when an abnormal con-
dition is detected.
Alarm: If active, alarms are annunciated on the com-
pressor HMI. When activated, a popup screen show-
ing the date and time of the alarm and alarm message
will appear. Alarms are also logged in the Event List.
An alarm serves only as a warning to the operator; if
an alarm is active the machine is still allowed to run.
Trip: If active, trips will shut the machine down or not
allow the compressor to start. Trips are annunciated
on the compressor HMI. When activated, a popup
screen showing the date and time of the trip and
trip message will appear. Trips are also logged in the
Event List.
The “Alarm Reset” pushbutton on the overview screen
will reset any active alarms or trips if the abnormal condi-
tion has been removed.
For a comprehensive list of alarms and trips and possible
causes, see the troubleshooting guide in this manual.
EMERGENCY STOP
Reference Figure 2-6
The Emergency Stop circuit in the compressor control
panel energizes the Master Control Relay, which pro-
vides power to PLC outputs that control actuators, heat-
ers, motor starters, valves, etc. The Master Control Relay
may be energized by pressing the “Control Power On
illuminated pushbutton on the door of the compressor
control panel. When the Master Control Relay is ener-
gized, the “Control Power On” pushbutton will illumi-
nate. The following conditions must be satis ed to en-
ergize the Master Control Relay:
Emergency Stop pushbutton on the door of the com-
pressor control panel must be pulled out.
Any additional Emergency stops or safety devices
tied in to the Emergency Stop circuit must be reset.
The compressor PLC must be booted up and
operational.
The 24-volt DC power supplies in the compressor
control panel must be powered up and OK.