7.3 Cannot edit device parameters in FDT Frame Application
Cannot edit device parameters in PACTwareFigure 7-4:
Check the Node ID in PACTware and the Device Address in the Fieldbus
Interface Configuration utility. The Node ID and Device Address should
match. You may need to manually enter the Node ID in PACTware. For
more information on entering the Node ID, see Section 6.3.
Update the DTM library. If a new DTM is added, you may need to update
the DTM library. For more information, see Section 6.2.
Check physical connections. Make sure all devices are properly connected
and have access to a power source. For more information, see Section 3.5.
Commission the fieldbus device. For more information, see Section 4.3.
User's Manual May 2014