Programming Battery Setup for the MPM
17-12
17.7. Battery Setup: Digital Output (MPM)
String View > Setup|Battery|Digital Output
The MPM has three optional relay contact control outputs you can define to trigger on an
alarm event.
Figure 58. Battery Setup - Digital Output (MPM)
After defining an Output Name and Trigger Name, the associated digital output can change
state on an alarm to control a user-selected device. If you select Latch, the output latches. The
relay is a Form C contact that de-energizes upon alarm condition reset.
Output Name - Type a name that describes the external device being controlled.
Trigger Name - From the drop-down list, select a parameter that energizes the
Control Output relay contact.
Enable - Select Enable to energize a rear panel Control Output contact on a trigger event.
Latch - When selected, the Control Output contact energizes until manually reset. If not
selected, the Control Output de-energizes when the trigger event clears.