Emerson BDS-256XL Guide de l'utilisateur Page 185

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 205
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 184
Commissioning Assistant
29-12
Click the Check Discharge Current button. Verify the ±15VDC voltage supply is
connected to the current transducer. Type the discharge current value in the Measured Value
field. The String Current (amps) field displays the millivolt value times the shunt value as
amps. If the measured value agrees with the calculated value in the monitor, the Status area
indicates Passed. If the measured value fails, calibrate the monitor to the measured value by
clicking the Cal button.
29.4.14. Check Test Current Screen
Figure 152. Check Test Current (Comm Asst)
Click the Check Test Current button. Before running this test, verify that all the voltages
across the load wires are correct. Failure to do this may result in severe damage to the load
module.
Select a load step from the Load Step spin box. Press the <Space Bar> to turn on the load,
and measure the load current. Type the value in the Measured Value field, then press
<Enter>. If the measured value agrees with the calculated value in the monitor, the Status
area indicates Passed. If the measured value fails, calibrate the monitor to the measured value
by clicking the Cal button.
Vue de la page 184
1 2 ... 180 181 182 183 184 185 186 187 188 189 190 ... 204 205

Commentaires sur ces manuels

Pas de commentaire