MPM Diagnostics
26-8
26.9. Intertier (MPM)
String View > Diagnostics|Intertier
The Intertier diagnostic monitors the signal on each intertier input. Use this diagnostic for
verifying the calibration of these input channels or troubleshooting. To open Intertier
Diagnostics, select Intertier.
Figure 122. Diagnostics - Intertier (MPM)
You may define up to eight intertiers for the MPM on the Battery Setup|Parameters dialog
box, but Intertiers 2 through 4 are active only when expansion ports J3, J4, J6 and J7 are
installed on the MPM.
Intertier Voltage (mvolts) - This column indicates the voltages being sent. This screen
displays up to eight intertiers for the MPM and is used to confirm calibration accuracy. The
cell number is the lower of the two cell numbers across which the intertier is connected
(selected on MPM Setup|Battery|Parameters).