Commissioning Assistant
31-12
Select a load step from the Load Step spin box. Press the <Space Bar> to turn on the load,
and measure the load current. Type the value in the Measured Value field, then press
<Enter>. If the measured value agrees with the calculated value in the monitor, the Status
area indicates Passed. If the measured value fails, calibrate the monitor to the measured value
by clicking the Cal button.