22
“S” RMS Shunt Power Fault
This fault is indicated by the display showing a “S”. This indicates a fault involving the
drives internal shunt circuitry. The shunt power parameter is an internally calculated
parameter.
Potential causes for the “S” High DC Bus fault
Internal shunt power calculation has exceeded capability of internal shunt circuitry
High Inertial load
High AC line
Short rapid moves coupled with very short deceleration ramps
“S” “RMS Shunt Power Fault”
Reset with
Reset P/B
Return
to
Normal Operation
High Interial
Load
Reduce
Load
Check for
Increase in
Acutal Load
High AC
Input line
Reset
with Reset P/B
Short Rapid
Moves coupled
with Very Rapid
Deceleration Ramps
> 264 VAC
Investigate Cause
for Increase
Yes
Monitor
AC Input
>264 VAC 47-63 Hz
Yes
No
Yes
No
No
Yes
Yes
Yes
No
"S"
RMS Shunt Power
Fault
Determine
which Motions
cause fault and
alter as needed
Returns
to
Normal Operation
Return
to Factory
End
No
Internal Shunt Power
Calculation exceeds
capacity of
intenal shunt circuitry