Emerson Bristol ControlWave Express Manuel d'instructions Page 71

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 88
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 70
ControlWave Express Instruction Manual (CI-ControlWave Express)
LED6
STA6
LED5
STA5
LED4
STA4
LED3
STA3
LED2
STA2
LED1
STA1
Status
In Hex
LCD
Display
Indication
Definition
0 0 1 0 1 1 0B INIT System Initialization in Progress
0 1 0 0 0 0 10 RECOV Waiting in Recovery Mode
0 1 0 0 1 0 12 RAMERR Error Testing SRAM
1 0 0 0 0 0 20 STOP Application Loaded
1 0 1 0 0 0 28 HALT Stopped at a Break Point
1 1 0 0 0 0 30 NO APP No Application Loaded
1 1 1 0 0 0 38 BREAKP Running with Break Points
1 1 1 0 1 1 3B POWERD Waiting for Power-down (after
NMI)
1 1 1 1 1 0 3E UPDUMP Waiting for Updump to be
Performed
1 1 1 1 1 1 3F NOTRUN Unit Crashed (Watchdog
Disabled)
In addition to the LEDs on the piggy-back LED board, the CPU/System
Controller board includes a watchdog LED (WD – CR1 right) and an
idle LED (IDLE – CR1 left) that have identical functions to WD and
IDLE described in Table 5-1.
Revised Mar-2011 Service & Troubleshooting 5-11
WD LEDIDLE LED
Figure 5-8. WD and IDLE LEDs