Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
3-22
Create and Send a Mass Flow Configuration using 3051S EA for
F
OUNDATION fieldbus
A mass flow configuration file can be created in either OFFLINE or ONLINE
mode.
1. Select the device tag name requiring a new or updated mass flow
configuration file. The selected device tag will become highlighted.
Information about the selected device will appear on the Device
Status portion of the screen.
2. Select the EA Wizard. A window stating, “Welcome to Rosemount
Engineering Assistant for F
OUNDATION fieldbus” will appear.
Figure 3-7. Open EA Wizard
3. 3.Select either “Start new file in Flow Wizard” or “Open existing
configuration files” in Flow Wizard. Select either create a new file or
open a current (saved) file and edit. Follow the EA Wizard and step
through completing a mass flow configuration (see page 3-33 for
details.)