Reference Manual
00809-0200-4801, Rev CA
July 2010
B-15
Rosemount 3051S
ASP Diagnostics Suite for FOUNDATION fieldbus
(Option Code D01)
The 3051S ASP Diagnostics Suite for F
OUNDATION fieldbus provides Abnormal Situation
Prevention indication and enhanced EDDL graphic displays for easy visual analysis.
The integral Statistical Process Monitoring (SPM) technology calculates the mean and
standard deviation of the process variable 22 times per second and makes them available to
the user. The 3051S uses these values and highly flexible configuration options for
customization to detect many user-defined or application specific abnormal situations (e.g.
detecting plugged impulse lines and fluid composition change).
Wireless Self-Organizing Networks
Output
WirelessHART, 2.4 GHz DSSS.
Local Display
The optional seven-digit LCD can display user-selectable information such as primary variable
in engineering units, percent of range, sensor module temperature, and electronics
temperature. Display updates at the user-configured update rate.
Update Rate
WirelessHART, user selectable 4 sec. to 60 min.
Power Module
Overpressure Limits Transmitters withstand the following limits without damage:
Coplanar Sensor Module (Single Variable)
In-Line Sensor Module
Field replaceable, keyed connection eliminates the risk of
incorrect installation, Intrinsically Safe Lithium-thionyl chloride
Power Module with polybutadine terephthalate (PBT)
enclosure. Ten-year life at one minute update rate.
(1)
(1) Reference conditions are 70 °F (21 °C), and routing data for three
additional network devices.
NOTE: Continuous exposure to ambient temperature limits of
-40 °F or 185 °F (-40 °C or 85 °C) may reduce specified life by less
than 20 percent.
Range
DP
(1)
& GP
(1) The overpressure limit of a DP Sensor with the P9 option is 4500
psig (310,3 bar). The overpressure limit of a DP Sensor with the
P0 option is 6092 psig (420 bar).
AP
3051S_CD, 3051S_CG
3051SMV_ _3 or 4
3051SF_3, 4, 7, or D
3051S_CA
0 750 psi (51,7 bar) 60 psia (4,13 bar)
1 2000 psi (137,9 bar) 750 psia (51,7 bar)
2 3626 psi (250,0 bar) 1500 psia (103,4 bar)
3 3626 psi (250,0 bar) 1600 psia (110,3 bar)
4 3626 psi (250,0 bar) 6000 psia (413,7 bar)
5 3626 psi (250,0 bar) N/A
Range
GP AP
3051S_TG 3051S_TA
1 750 psi (51,7 bar)
2 1500 psi (103,4 bar)
3 1600 psi (110,3 bar)
4 6000 psi (413,7 bar)
5 15000 psi (1034,2 bar)