System and Control Options
47 Liebert
®
Universal Monitor
9.3.4 Set Up Alarmable Inputs in Latched or Unlatched Mode
Alarmable input points may be set up in Latched mode (Y), which
requires the user to clear the Liebert Universal Monitor alarms after
an alarm has occurred, or Unlatched mode (N), in which alarms will
automatically clear after a return-to-normal state. The default setting
for alarmable inputs is N (Unlatched). Any input defined as an event
is automatically Unlatched.
A digital input defined as Latched does not reset automatically after
an alarm. It will remain in the triggered position even after the
monitored device returns to normal. After an alarm, the user must
manually reset Latched inputs, as described in 9.12.1 - Clear Active
Alarms. This also means that any digital outputs linked to a Latched
digital input will remain triggered until the input is manually reset.
A digital input defined as Unlatched will automatically track the
status of the monitored device. No action by the user is required.
From the Setup Input Menu, choose Latched, as shown above
right, and press Enter .
To change this feature, use the arrows
↑↓ to choose Y (Yes -
Latched) or N (No - Unlatched), then press Enter .
NOTE: Only alarmable input points may be set up as Latched. If you
attempt to set up an event as Latched, the message shown at right
appears. Press the ESC key to return to the previous screen to
continue configuring the digital input.
The only way to reset latched alarms is by clearing active alarms. This
step is required to return latched points to their normal state. For
details, see 9.12.1 - Clear Active Alarms.
9.3.5 Set Up Delay Time
Each input may be set up with a specified time delay between the
occurrence of an alarm or event—a monitored device changes state—
and any response by the Liebert Universal Monitor. This feature can
prevent needless responses to transient conditions.
This delay is the amount of time that must elapse before the Liebert
Universal Monitor acknowledges the change of state in the monitored
device and takes any further action, such as dialing configured pagers.
The default time delay is 1 second (displayed as 00 MIN : 01 SEC).
The time delay applies only when a monitored device changes from its
normal state—for example, the Liebert Universal Monitor detects a
closed contact that is defined as Normally Open.
When the monitored device returns to its normal state, the Liebert
Universal Monitor acknowledges the change of state immediately.
From the Setup Input Menu, choose Delay, as shown at right, and
press Enter .
To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):
For minutes (MIN), press and hold one of the arrow keys
↑↓ scroll through the numbers 00-99.
Press Enter to advance to seconds (SEC).
For seconds (SEC), press and hold one of the arrow keys
↑↓ scroll through the numbers 00-59.
When finished, press Enter again.
Setup Input Menu
SETUP INPUT_01
LABEL: INPUT_01
NORM OPEN/CLOSE: NO
ALARM/EVENT: AL
↑↓=NEXT =SELECT
> LATCHED: N
DELAY: 00:01
Latched / Unlatched
IS ALARM
LATCHED? N
↑↓=Y/N =END
Message (if input has
been defined as an event)
LATCH NOT ALLOWED
WHEN IN EVENT MODE
ESC=BACK
Setup Input Menu
SETUP INPUT_01
LABEL: INPUT_01
NORM OPEN/CLOSE: NO
ALARM/EVENT: AL
↑↓=NEXT =SELECT
LATCHED: N
DELAY: 00:01
Delay Time
DELAY TIME BEFORE
TRIGGER?
00
MIN : 01 SEC
↑↓=SELECT
=NEXT/END