Emerson Bristol ControlWave ExpressPAC Manuel d'instructions Page 83

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 96
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 82
ControlWave ExpressPAC Instruction Manual (CI-ControlWave EPAC)
Figure 5-9. Communications Diagnostic Menu
3. Enter 5 in the Number of Passes field.
4. Select a port to test (click to display all available ports).
Note: The port you select must correlate to the port on which you
placed the loop-back plug in step 1.
5. Select 115200 or ALL ASYNC as the baud rate (click to
display all available rates).
6. Click RUN to start the test. At the completion of the test (which
generally takes about 5 seconds), any failed results appear in the
Status field to the right of the RUN button:
TXD RXD Failure
CTS RTS Failure
7. Click Return to Menu to display the WINDIAG Main Menu.
5.4 Core Updump
In some cases—such as when a ControlWave ExpressPAC fails for no
apparent reason—you can upload a copy of the contents of SRAM and
SDRAM to a PC for support personnel and service engineers to
evaluate. This upload is called a “core updump.”
Revised Mar-2011 Service & Troubleshooting 5-15