Page 2 - Table of Contents

When the HART Communicator is connected to the transmitter and turned on, the first screen that is seen by the user is the root menu screen. If the tr

Page 3 - LTM-300 Mounting Configuration

If the user selects Operation Status from the Diagnostics screen, he is able to view all of the status bits indicating the health of the transmitter o

Page 4 - 2.1 Theory of Operation

The HART Communicator informs the user that the maintenance flags have been reset when the transmitter has replied to the reset command. The user must

Page 5

If it is desired to trim the digital level value, he may select a single point zero trim or a full level trim that requires the input o

Page 6

Starting at the Calibration screen, select the Zero Level Trim procedure. This procedure trims the Level digital value measurement at the position th

Page 7

The HART Communicator now requests that the level float be set to the desired level upper trim point. The second trim point can be any other level poi

Page 8 - CAUTION:

The user is then notified that the loop may now be returned to automatic control. After the user presses OK the HART Communicator returns to the Calib

Page 9

The user is then notified that the loop may now be returned to automatic control. After the user presses OK the HART Communicator returns to the Calib

Page 10 - Diagnostics and Service

The HART Communicator will display this screen reminding the user that the loop should be removed from automatic control before proceeding. When this

Page 11

The next screen gives the user a choice to set the 4mA or 20mA values or to Exit the procedure. Here the user will select the 4mA menu position.The H

Page 12

LTM-300 Magnetostrictive Level Transmitter Instruction and Maintenance ManualTable of ContentsSection 1. Transmitter Overview Page1.0 Gener

Page 13



Page 14 - Full Level Trim

The LTM-300 is an electronic field instrument, suitable for installation in hazardous and non-hazardous industrial areas. Testing and certi

Page 15 - Zero Temperature Trim

The LTM-300 is an assembly of two major components:• The Sensor Tube Assembly. This a 5/8” diameter stainless steel probe, sealed on one end, with t

Page 16 - Full Temperature Trim

Level/Interface. A second float may be added below the first one, and the second output will be calibrated automatically. The second time interval

Page 17 - Basic Setup Procedures

Ambient Temp. Range -20°C ... +40°C (-4°F ... 104°F)Humidity Limits: SAMA PMC 31.1-5.2Vibration Limits:

Page 18 - Reranging the Transmitter

DisplaysLevel Measurement Display - in inchesLevel measurement Display - in centimetersLevel Measurement Display - in millimetersLevel Measurement Di

Page 19 - Detailed Setup Selections

6.4 Start-Up for Gage-MountedLTM Transmitters If the transmitter does not appear to calibrate properly, or has an erratic output, check the deadb

Page 20 - 

All MagTech products are warranted against defects in materials and workmanship of one year from date of shipment. The level gage chamber and process