Vission 20/20 Retrofit Instructions
10ViSSion® 20/20 Retrofi t Instructions • 35391SCRFStep 2. An auxiliary contact from compressor motor starter is required. Connect isolated contact t
11ViSSion® 20/20 Retrofi t Instructions • 35391SCRFStep 4. A dry contact from control relay CR12 must be wired to oil pump motor starter coil. This d
12ViSSion® 20/20 Retrofi t Instructions • 35391SCRFTorque Specifications (ft-lbs)TypeBoltHeadMarkingsNominal Size Numbers or Inches#10 1/4 5/16 3/8 7/1
35391SCRF Rev. 1 (4/13) Emerson and Vilter are trademarks of Emerson Electric Co. or one of its affi liated companies. © 2012 Emerson Climate Technolog
3ViSSion® 20/20 Retrofi t Instructions • 35391SCRFTable of ContentsSections Page1.0 General Information ...
4ViSSion® 20/20 Retrofi t Instructions • 35391SCRF2.0 Vission 20/20 Retrofi t Instructions This procedure defi nes the steps required to replace a Vilt
5ViSSion® 20/20 Retrofi t Instructions • 35391SCRF2.2 InstallationNOTETorque all hardware according to torque table specifi cations, see Table 1.NOTEMod
6ViSSion® 20/20 Retrofi t Instructions • 35391SCRFStep 8. Install hardware to secure new vibration isolators (5) to mounting holes of Vission 20/20 mi
7ViSSion® 20/20 Retrofi t Instructions • 35391SCRFNOTEStainless steel tubing is not provided in a retrofi t kit.Step 10. Route stainless steel tubing f
8ViSSion® 20/20 Retrofi t Instructions • 35391SCRFStep 12. Connect cables (10) to transducers (7).Figure 6. Block and Bleed Assembly with Transduce
9ViSSion® 20/20 Retrofi t Instructions • 35391SCRFCAUTIONDo not route A/C and D/C wires together, this willcause Electromagnetic Interferance. Failure