Parameters - XR570C - XR570D – XR572C - Continued
Use fold out programming flow chart inside front cover
Fdt Drip Time Sets the period of time following the termination of a defrost during
which period nothing happens. This allows any residual moisture on
the evaporator time to drip down and drain away.
0 ÷ 255 mins.
Pr2 0
dPO First Defrost
after start up
Tells the controller whether to do an immediate defrost when the
power is switched on or to wait for the normal interval time as set in
parameter IdF. Can be used to make sure defrosts are not missed in
areas with unreliable power supplies.
0=immediate
1=After IdF
time
Pr2 1
FnC Fan
Operating Mode
Tells the evaporator fan to either run continuously ( apart from
during defrost ) or to cycle on and off with the compressor.
0=cycle with
compressor
1= Continuous
Pr2 1
Fnd Fan Delay Sets the time between the end of defrost and the evaporator fans re-
starting.
0 ÷ 255 mins.
Pr2 10 mins.
FSt Fan Stop
Temperature
Sets the maximum temperature ( sensed by the evaporator probe )
above which the controller stops evaporator fans from running
- 50 c ÷ 50 c
Pr2 - 1 c
Ot Thermostat
Probe Calibration
Enables the controller to be re-calibrated or off-set from the probe
temperature reading.
- 30 c ÷ 30 c
Pr2 0
OE Evaporator
Probe Calibration
Adjusts the off – set of the evaporator probe
- 30 c ÷ 30 c
Pr2 0
rES Resolution Turns the decimal point on or off. This gives a display resolution of
either 1 degree or 0.1 degree Celsius.
0=Off
1=On
Pr2 1
CF Unit of
Measurement
Sets the display to read out in Celsius or Fahrenheit 0=Degrees C
1=Degrees F
Pr2 0
COn Probe Fault
“ON”
Time
If a probe fault is detected the display will flash P1 and the controller
will automatically cycle the compressor on and off. This parameter
sets the “ON” time period
0 ÷ 255 mins.
Pr2 15 mins.
COF Probe Fault
“OFF”
Time
If a probe fault is detected the display will flash P1 and the controller
will automatically cycle the compressor on and off. This parameter
sets the “OFF” time period
0 ÷ 255 mins.
Pr2 30 mins.
dIC Digital input
mode
Configures controller’s response to an input on “Digital input 1”
0 = Generic alarm. Display will flash “EA, alarm sounds and
alarm relay operates, controller continues to control as normal
1 = Important alarm. Display will flash “CA”, alarm sounds and
alarm relay operates, controller relays open to stop all functions.
2 = Serious alarm. Display will flash “OFF”, alarm sounds and
alarm relay operates, controller relays open to stop all functions.
3=External consent for defrost end: See technical manual
0 = Generic
1 = Important
2 = Serious
3=External
consent
Pr2 0
dId Digital input
delay
Sets the delay between an input being detected by “Digital input 1
and the alarm being activated.
0 ÷ 255 mins.
Pr2 5 mins.
dOA Open door
alarm delay
Sets the delay between an input being detected by “Digital input 2”
and the “Door Open” alarm being activated. ( XR572C only )
0 ÷ 255 mins.
Pr2 15mins.
tBA Alarm Mute
On / Off
Allows or prevents muting of the alarm buzzer and alarm relay.
0 = Alarm cannot be muted, 1 = Alarm can be muted
0=Mute disable
1=Mute enable
Pr2 1
Ad 1-Ad 2 Serial
Address
This is only utilized when the instrument is being used as part of a
networked control system together with other controllers, all linked
back to a monitoring panel. It gives the controller it’s system address.
0 ÷ 94
Pr2 0 / 1
Ptb Parameter
Table
Shows in sequence every parameter’s label and then displays the
factory default setting for that parameter.
- - - Pr2 - - -
Continued overleaf:-