- 13 -
Parameters - XR160C – XR170C – XR162C – XR172C
-
XR160D –
XR170D Controllers with forced defrost & fan delay
Use fold out programming flow chart inside front cover
Parameter &
Label
Description Range Pr1
Pr2
Factory
Default
SP Set Point Sets the temperature at which the compressor stops LS to US Pr1 - 5 c
HY Differential Sets the number of degrees above Set Point at which the compressor
is re-started
0 2 °÷ 12 0 c
Pr1 2 c
LS Lower Set
Point Limit
Sets the lowest temperature to which the customer can adjust the Set
Point
- 57 c ÷
Set Point
Pr2 - 30 c
US Upper Set
Point Limit
Sets the highest temperature to which the customer can adjust the Set
Point
Set Point ÷ 99 c
Pr2 20 c
AC Anti Short
Cycle
Sets the minimum time period between the stopping of the
compressor and it’s next possible restart
0 ÷ 30 mins.
Pr2 1 min.
ALC Alarm
Configuration
Configures the alarm either to absolute temperatures or
to be relative to the Set Point ( i.e. so many degrees
above & below Set Point ) If “Relative”, when the Set Point is
altered the alarm levels will follow it
Note: (Only for XR150C with alarm relay):-
0 & 1 – Muting buzzer de-activates alarm relay
2 & 3 – Muting buzzer leaves alarm relay activated
0=Relative
1=Absolute
2=Relative
3=Absolute
Pr2 0
ALU Alarm
Level Upper
Sets the high temperature alarm level. If ALC=0 it sets how many
degrees above Set Point. If ALC=1 it sets a fixed alarm temperature.
Set Point ÷ 99 c
Pr2 10 c
ALL Alarm
Limit Lower
Sets the low temperature alarm level. If ALC=0 it sets how many
degrees below Set Point. If ALC=1 it sets a fixed alarm temperature.
-57c ÷ Set Point
Pr2 10 c
Ald Alarm Delay Sets the time delay between a temperature alarm condition being
sensed and the alarm being signaled during normal operation.
0 ÷ 120 mins.
Pr2 15 mins.
dAO Alarm
Delay at Start Up
Sets the initial temperature alarm delay time on start up so avoiding
unnecessary alarms during pull down.
0 ÷ 720 mins.
Pr2 90 mins.
Ods Delay of
Outputs on Start
Up
Sets the time delay between the power to the controller being turned
on and any output relay starting to operate. This can be used to
prevent short cycling of the compressor following a momentary
power failure.
It can also be used to stagger the re-start of multiple units following a
power failure, to prevent everything trying to start at once and
blowing a fuse.
0 ÷ 120 mins.
Pr2 1 min.
CCt Fast Chill /
Freeze
The controller has a thermostat override facility. This parameter sets
the override time during which the compressor will run continuously
irrespective of the temperature. Setting time to 0 to disables this
function
0 ÷ 990 mins.
Pr2 240 mins
dAF Delay of
Defrost after fast
chill
Sets the period of time following a thermostat override after which
the controller will go into a defrost. The controller will then resume
normal operation
0 ÷ 120 mins.
Pr2 120 mins.
IdF Interval
Between defrosts
Sets the interval time between the start of successive defrosts
1 ÷ 120 hours
Pr2 6 hours
dSd Delay start
of defrost
When a defrost is due to commence ( after the IdF time), this
parameter adds a period of time during which the start of defrost is
delayed. Used to stagger defrosts between multiple controllers
0 ÷ 59 mins
Pr2 0 mins.
n
dF Length
Of Defrost
Sets the maximum duration time of the defrost
0 ÷ 120 mins.
Pr2 30 mins.
dtE Defrost
Termination
Temperature
Sets the evaporator temperature at which the controller will terminate
the defrost. This temperature is sensed by the evaporator probe.
- 57 ÷ 50 c
Pr2 8 c
dFd Display
During Defrost
This tells the controller what to display during defrost.
0 = Actual temperature, 1 = Temperature at start of defrost,
2 = Set Point, 3 = “DEF” label
0
1
2
3
Pr2 1
dAd Max display
after Defrost
After defrost, the temperature as it was at commencement of defrost
is displayed. Normal display is resumed once the actual temperature
drops below this point or the time set in this parameter has expired
0 ÷ 120 mins.
Pr2 30 mins.
tdF Defrost Type Configures the controller for defrost by electrical heaters or hot gas.
If set for hot gas, the compressor is kept running during defrost.
* Settings 2 & 3 are for special applications only. Refer to
manufacturer’s manual
0=Electrical
1=Hot Gas
2=*
3=*
Pr2 0