ControlWave Gas Flow Computer (GFC Plus) Instruction Manual (CI-ControlWave GFC Plus)
Revised Feb-2013 Service & Troubleshooting 5-17
Note: The port you select must correlate to the port on which you
placed the loop-back plug in step 1.
5. Select 115200 or ALL ASYNC as the baud rate (click to
display all available rates).
6. Click RUN to start the test. At the completion of the test (which
generally takes about 5 seconds), any failed results appear in the
Status field to the right of the RUN button: For example:
TXD RXD Failure
CTS RTS Failure
7. Click Return to Menu to display the WINDIAG Main Menu.
5.5 Core Updump
In some cases—such as when a ControlWave GFC Plus fails for no
apparent reason—you can upload a copy of the contents of SRAM and
SDRAM to a PC for support personnel and service engineers to
evaluate. This upload is called a “core updump.”
A core updump may be required if the ControlWave GFC Plus
spontaneously enters a watchdog state that affects all system operation.
This occurs when the system crashes as a result of a CPU timeout
(resulting from improper software operation, a firmware glitch, and so
on). In some cases, the watchdog state can recur but you cannot
logically reproduce the conditions.
The CPU’s RAM contains “crash blocks,” a firmware function provided
specifically for watchdog troubleshooting. You can view and save the
crash blocks by viewing the Crash Block Statistic Web Page (see the
Web_BSI Manual, D5087). On request, you can forward crash block
files to our technical support personnel. If they need additional
information to evaluate the condition, the technical support group may
request a core updump. Once the core updump process generates a file,
you can forward that file to the support personnel for evaluation and
resolution.
Use the following steps to preserve the “failed state” condition at a
system crash and perform a core updump:
1. Set switch SW2-1 on the CPU/System Controller board to OFF
(Disable Watchdog Timer). Set switch SW2-4 to OFF (Enable
Core Updump).
Note: The factory default setting for switch SW2-4 is OFF.
2. Wait for the error condition (typically“NOTRUN” on the LCD
display).
3. Connect the ControlWave GFC Plus’ Comm Port 1 to a PC
using a null modem cable.
4. Set the ControlWave GFC Plus for Recovery Mode by setting