Fisherr Z500 Severe Service Ball Valves
Contents
Introduction 1.................................
Scope of Manual 1.............................
Description 1.................................
Specifications 1...............................
Installation 5
....................................
Operation 7...................................
Maintenance 8
..................................
Troubleshooting 9.............................
Packing Replacement 10.......................
Actuator Mounting 13.........................
Parts Ordering 18
................................
Parts List 18.....................................
Figure 1. Fisher Z500 Severe Service Ball Valve
X1200
Introduction
Scope of Manual
This instruction manual provides installation, operation, maintenance, and parts information for the Fisher Z500
Severe Service Ball Valve (see figure 1).
Do not install, operate, or maintain Z500 valves without being fully trained and qualified in valve, actuator, and
accessory installation, operation, and maintenance. To avoid personal injury or property damage, it is important to
carefully read, understand, and follow all the contents of this manual, including all safety cautions and warnings. If you
have any questions about these instructions, contact your Emerson Process Management sales office
before
proceeding.
Description
The Z500 severe service ball valve is a split body bolted design, full or reduced port, with a blowout proof stem. It can
be lever operated, gear operated, or actuated. The Z500 severe service ball valve line is a simplistic two-piece floating
ball design with integral metal seat meant to provide tight metal seating shutoff in high temperature, high pressure,
corrosive, and erosive applications across all industries.
Specifications
Specifications for these valves are shown in table 1.
Instruction Manual
D103803X012
Z500 Valve
April 2015 - rev B
Vue de la page 0
1 2 3 4 5 6 ... 19 20

Résumé du contenu

Page 1 - Introduction

www.Fisher.comFisherr Z500 Severe Service Ball ValvesContentsIntroduction 1...Scope of Manual 1...

Page 2

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B10Figure 2. Bolting Tightening Pattern111222333444556678Valve Leaking through Ball or Seating

Page 3

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B11Figure 3. Sectional ViewBODYSTUD/NUTSTEMSEAT HOLDERSIDE-MOUNTEDBRACKETX1207UPSTREAMSEATBELL

Page 4

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B121. Loosen the packing studs.2. Remove the packing rings from the packing box, being caref

Page 5 - Installation

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B13Figure 6. Use Packing Flange8. Bolt up the packing flange. Use Belleville washers in the s

Page 6 - Weld End Valves

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B14Figure 8. Mount the Stem AdapterFigure 9. Position the Mounting Bracket3. Place the actuat

Page 7 - Operation

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B15Figure 10. Place the Actuator on Top of the Mounting BracketFigure 11. Install the Handwhee

Page 8 - Maintenance

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B16Figure 12. Stem Adapter9. Place the lock plate on top of the mounting bracket. Note the

Page 9 - Troubleshooting

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B17Table 5. Packing Flange Bolt Torque ValuesBOLT SIZE RECOMMENDED TORQUEmm Inch lbf•ft lbf•in

Page 10 - Packing Replacement

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B18Parts OrderingA serial number is assigned to each valve and stamped on the nameplate. Alway

Page 11 - Instruction Manual

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B19Figure 15. Fisher Z500 Valve Assembly

Page 12

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B2Table 1. SpecificationsValve SizesZ500: NPS J 1/2, J 3/4, J 1, J 1-1/2, J 2, J 3,J 4, J 6, J

Page 13 - Actuator Mounting

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B20Emerson Process Management Marshalltown, Iowa 50158 USASorocaba, 18087 BrazilChatham, Kent

Page 14

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B3Table 2. Valve Body Materials, End Connections, and RatingsRatings Bore Size, NPS End Connec

Page 15 - Hand Lever

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B4Table 2. Valve Body Materials, End Connections, and Ratings (continued)Ratings Bore Size, NP

Page 16

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B5Installation WARNINGAlways wear protective gloves, clothing, and eyewear when performing an

Page 17

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B6d. Customer shall ensure valve stem has not been pushed or forced down into the valvee. Cu

Page 18 - Parts List

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B7ProcedureInitial Preparation1. Ensure the valve is in the fully open position so that vital

Page 19

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B82. Actuators supplied with the valve may require maintenance per the actuator manufacturer&

Page 20

Instruction ManualD103803X012Z500 ValveApril 2015 - rev B9TroubleshootingOperationD Stem adapter/actuator may be misaligned-- Remove actuator and stem