compressor OFF. In the case where the module is set
for failsafe OFF the compressor will not run until
communications have been re-established with the
E2. In the case where the module is set for failsafe
ON, the compressor will continue to run until commu-
nications have been re-established with the E2. In this
case all compressor protection provided by the mod-
ule will still function as needed.
Each module is sent from the Emerson Climate
Technologies, Inc. factory with the failsafe set “ON”.
To check this setting or to program the module for fail-
safe OFF, follow these steps:
1. Starting at the main menu, press 5 (Configured
Applications) then 35 (ISD Compressor).
2. Select the desired ISD device and press F5:
Setup. The following screen should be displayed:
Figure 3.14 ISD Setup Screen (General)
3. Select Compressor On or Compressor Off
depending on the desired failsafe.
4. Repeat this for each ISD module.
3.8 Remote Reset
In the event of an oil pressure or discharge tempera-
ture lockout a manual reset is required to restart the
compressor. This can be accomplished by pressing
the reset button on the front of the Intelligent Store™
Discus® module or by remotely resetting the module
through the CPC UltraSite™ monitoring software
program. To enable this remote reset option, access
the ISD Compressor Setup Screen by following these
steps:
1. Press menu to open the Main Menu.
2. Press 5 (Configured Applications).
3. Press 35 (ISD Compressor).
4. Press F2 (Next Tab) to access the Alarm Tab.
The screen should look like figure 3.15 below.
Change the selection next to Oil Lock Reset to
“Enabled”. Repeat these steps for each module.
Figure 3.15 ISD Setup Screen (Alarms)
3.9 ISD Module Status
To serve as a convenient and quick reference, the E2
will display information about each ISD module. To
access this screen follow these steps:
1. Starting at the main menu, press 5 (Configured
Applications).
2. Press 35 (ISD Compressor).
3. Select the desired ISD device and press Enter.
The display should look like figure 3.16 below.
Figure 3.16 ISD Status Screen
AE8-1337 R1