
14
This will open the suction group setup screen as
shown below in figure 3.6:
Figure 3.6 Suction Group Setup Screen
From this screen you can edit the name of the suction
group, select the control type, and enter the number
of stages. The number of stages can be determined
as follows. A compressor with an unloader will
account for two stages. A compressor without an
unloader will count as one stage.
To continue the suction group setup process:
1. Press F2 (Next Tab) until the Comp Setup screen
is displayed.
2. Under Type, select Comp for compressor or Unld
for unloader.
3. Under HP/Amps enter the compressor horsepow-
er for each stage.
4. If run proofing is desired, select Yes under Proof.
Note: For a compressor equipped with an unloader
the horsepower should be divided between the
compressor and unloader stages. A compressor with
an unloader can be considered to be two different
compressors from a control standpoint. When the
suction group status screen shows the unloader to be
“off” and the comp (compressor) to be “on”, the
compressor is running “unloaded”, i.e. the unloaded
portion of the compressor is not contributing to gener-
ation of capacity (this is confusing since the unloader
solenoid in this case is actually “on”). If the comp and
unloader are both “on”, the compressor is running at
full capacity.
Sample Rack with Intelligent Store™ Discus® Compressors
- 25° Suction - 15° Suction
4DL3A150L-TSK
04I35625R
3DRHA100E-TFD
04I00300R
4DS3A220E-TSK
04I35631R
3DRHA100E-TFD
04I00439R
2DC3-050E-TFD
04I00435R
Subnet: 15
Node: 2
Subnet: 15
Node: 5
Subnet: 15
Node: 4
Subnet: 15
Node: 3
Subnet: 15
Node: 1
RACK1COMP1 RACK1COMP2 RACK1COMP3 RACK2COMP1 RACK2COMP2
Comp1
Address
Compressor
Name
Stages
Comp2
Comp3
(unloader)
Comp4
Comp5
(unloader)
Comp1
Comp2
(unloader)
Comp3
Figure 3.7 Suction Group Setup Screen (Comp Setup)
Commentaires sur ces manuels