Startup, Adjustment, and Shutdown
CAUTION
If required, tank vents (normal
and emergency) must be in place
and operating.
Startup
CAUTION
Always open the tank shutoff valve prior
to the inlet shutoff valve. Failure to do
so could result in inlet pressure being
applied to the actuator casing, potentially
damaging it. Refer to Figure 5.
1. Open the tank and sensing line shutoff valves
(between the Type ACE97 valve and tank).
2. A tank vapor space pressure gauge should be
installed and visible.
3. Slowly open the inlet shutoff valve (to the pad
valve) and leave it fully open.
4. Monitor the tank vapor space pressure.
Adjustment
The setpoint of this unit is factory set. If an adjustment
is to be made, it should be made in small increments
while the unit is controlling tank pressure. It is difcult
to make eld adjustments due to the slow changes in
tank pressure.
To change the pad (blanketing) setpoint:
1. Disconnect the tubing from the depad pilot valve
(See Figure 6).
2. Loosen the locknut (See Figure 7), but maintain its
position in relation to the adjusting coupling.
Doing so leaves the depad setpoint unchanged.
3. Separate the depad pilot valve from the actuator
by unthreading and removing.
4. Unthread and remove the adjusting coupling.
5. Increase the pad setpoint by turning the adjusting
screw clockwise. (Turning the screw counterclockwise
decreases the setpoint). See Figure 7.
6. Replace the depad adjusting collar against the
locknut to re-establish the depad setpoint.
To change the depad setpoint:
1. Loosen the locknut below the adjusting coupling.
2. Rotate the collar to change the setpoint. (The
bottom of the coupling—nearest the locknut—is
left-hand threaded).
3. Tighten the locknut.
E0679
Figure 7. Changing the Pad Setpoint
ADJUSTING SCREW
LOCKNUT
Figure 6. Unthreading the Adjusting Coupling
E0678
TUBING
COUPLING
ACTUATOR