Reference Manual
00809-0100-4803, Rev DA
Section 3: Configuration
April 2013
Configuration
Note
The transmitter may be equipped with either an absolute or gage static pressure sensor type
depending on specified model code. The type of static pressure sensor equipped in the
transmitter can be determined by referring to the Static Pressure Sensor Type heading. The static
pressure type not being measured is a calculated value using the atmospheric pressure value as
specified under the User-Defined Atmospheric Pressure heading.
2. The Sensor Limits and Minimum Span for the absolute and gage static pressure can be
viewed under the Sensor Limit headings.
3.7.6 Process temperature
Note
For Process Temperature Sensor Calibration see page 9.
If a transmitter was ordered with Fixed Process Temperature Only, the Fixed Temperature Value
and Units can be edited on the Fixed Temperature tab.
Figure 3-36. Variables - process temperature tab
1. Under the Process Temperature Setup heading, edit the Units and Damping value as
needed.
2. Select the Temperature Mode under the Process Temperature Setup heading. See
Tab le 3 -1 2.
Mass and Energy Flow Fast Keys 1, 4, 1, 6
Direct Process Var. Output Fast Keys 1, 4, 1, 3