Reference Manual
00809-0100-4801, Rev FA
October 2010
7-17
Rosemount 3051S Series
Reset
If SPM trip action is set to “Alert Latched”, clicking on Reset will clear the alert
when process conditions are back to normal or baseline.
Relearn
Clicking this button will cause SPM to relearn the process condition and
establish a new baseline. Manually performing a relearn is recommended if
the process profile has been intentionally changed to a new set point.
Figure 7-15. Operational Values
screen
The Operational Values screen contains the parameter values used in the
SPM diagnostic.
Standard Deviation
This is the current value of standard deviation. This value is continuously
calculated and can be provided as a secondary variable.
Mean
This is the current value of mean. This value is continuously calculated
and can be provided as a secondary variable.
Coefficient of Variation
This is the current value for coefficient of variation. The CV is derived from
the ratio of standard deviation to mean. This value is continuously
calculated and can be provided as a secondary variable.
Number of Relearns
This is the number of times SPM relearn has been initiated by the user or
via automatic relearn.
Detection
If the SPM diagnostic detects a Standard Deviation, Mean, or Coefficient of
Variation change outside the threshold values, the SPM Status box will
indicate “Detection”, followed by the type of detection.