Reference Manual
00809-0100-4801, Rev FA
October 2010
Rosemount 3051S Series
6-4
Switches installed
1. If using a communicator, use the following fast key sequence to set the
Alarm and Saturation values.
Alarm Levels - Fast Key; 1, 4, 2, 7, 7
Saturation Levels - Fast Key; 1, 4, 2, 7, 8
2. Manually set the direction for the Alarm to HI or LO using the ALARM
switch as shown in Figure 6-2.
Switches not installed
3. If using a communicator, use the following fast key sequence to set the
Alarm and Saturation values and the Alarm Direction:
Alarm Levels - Fast Key; 1, 4, 2, 7, 7
Saturation Levels - Fast Key; 1, 4, 2, 7, 8
Alarm Direction Fast Key; 1, 4, 2, 7, 6
Figure 6-2. Security and alarm
configuration (option D1)
Security
Alarm