20 Chapter 2 Battery
NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual
2.5 Battery Recycling
If the battery leaks electrolyte, or is otherwise physically damaged, it should be placed in a container resistant to
sulfuric acid and disposed of in accordance with local regulations.
Disused lead-acid storage battery belongs to dangerous waste, and it is a key item for disused battery pollution
control. The storage, transportation, use and disposal of the battery shall comply with the national and local laws and
regulations on dangerous waste and disused battery pollution prevention and other standards.
According to the relevant national regulations, the disused lead-acid storage battery must be recycled and shall not
be disposed of with other methods. Random discard or any other improper disposal of the disused lead-acid storage
battery may cause severe environment pollution and the relevant person will be investigated of corresponding legal
responsibilities.
As a lead-acid storage battery supplier, Emerson has built a perfect service network and disused battery recycling
system to help the customer legally and properly dispose of the lead-acid storage battery. For detailed information
about the disused battery recycling system of Emerson, please consult the local customer service center or sales
office of Emerson. If the customer refuses to accept this special note or does not use the disused battery recycling
system of Emerson. Emerson will not undertake any environment responsibility caused by the improper disposal of
the disused battery products.
2.6 Connection Of External Battery Circuit-Breaker (BCB
Table 2-1 provides recommended BCB rated current and minimum connection cable Cross Sectional Area (CSA).
Table 2-7 Reference table for selection of BCB rated current and connection cable CSA (minimum recommended)
Note: the minimum CSA is adequate for batteries located up to 5 meters from the UPS. For longer cable runs, the CSA shall be increased so
that the voltage drop remains less than 1% in order not to affect the battery run time significantly.
Item Unit UPS rating (kVA)
30 40 60 90, 100 120 150, 160 200
30-cell
battery
Maximum battery discharge
current at full load
A 105 140 210 315 420 525 630
Reference rated current of BCB A 150 175 250 350 450 550 700
Connection cable CSA mm
2
35 50 70 120 150 185 240
32-cell
battery
Maximum battery discharge
current at full load
A 100 133 200 300 400 500 590
Reference rated current of BCB A 150 150 250 350 450 550 630
Connection cable CSA mm
2
35 50 70 120 150 185 240
34-cell
battery
Maximum battery discharge
current at full load
A 94 125 186 282 376 470 556
Reference rated current of BCB A 100 150 200 300 400 500 630
Connection cable CSA mm
2
35 50 70 95 120 185 200
36-cell
battery
Maximum battery discharge
current at full load
A 88 118 176 264 352 440 525
Reference rated current of BCB
A 100 125 200 320 400 500 550
Connection cable CSA
mm
2
25 35 50 95 120 150 200
38-cell
battery
Maximum battery discharge
current at full load
A 84 112 168 252 336 420 498
Reference rated current of BCB A 100 125 200 260 350 450 550
Connection cable CSA mm
2
25 35 50 95 120 150 200
40-cell
battery
Maximum battery discharge
current at full load
A 80 106 160 240 320 400 473
Reference rated current of BCB
A 100 125 200 250 320 400 500
Connection cable CSA
mm
2
16 25 35 70 95 120 180
Note:
-It is recommended to use a DC moulded-case circuit breaker (MCCB) appropriately rated to open the kA fault current of the
battery at the nominal battery voltage. Applicable connections between the battery, BCB and UPS are shown in Figure 2-3, 2-4
and 2-5.