6 Chapter 1 Installation Of UPS Module
NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual
1.5.1 Rectifier And Bypass Input
Over currents
Install suitable protective devices in the distribution of the incoming mains supply, considering the power cable
current-carrying capacity and overload capacity of the system (see Table 8-6). Generally, magnetic circuit breaker
with IEC60947-2 tripping curve C (normal) at 125% of the current listed in Table 1-1 is recommended.
Split bypass: In case a split bypass is used, separate protective devices should be installed for the rectifier input and
bypass input in the incoming mains distribution panel.
Note
1. The rectifier input and bypass input must use the same neutral line.
2. For IT power systems, four-pole protective devices must be used upstream of the input distribution panel and output distribution
panel, external to the UPS.
Earth leakage
The residual earth current introduced by the radio frequency interference (RFI) suppression filter inside the UPS is
greater than 3.5mA and less than 1000mA. It is recommended that the sensitivity of all differential devices be verified
upstream of the input distribution panel.
1.5.2 External Battery Circuit Breaker
The UPS and its associated battery are protected against the effect of overcurrents through a DC circuit breaker
provided by the external battery cabinet.
The rated voltage of the external battery overcurrent protective device is more than 500Vdc, and its DC breaking
current is more than 8kA.
1.5.3 UPS Output
The UPS output distribution shall be configured with a protective device. The protective device shall be different from
the input distribution protection switch and able to provide overload protection (refer to Table 8-6).
1.6 Power Cables
The cable design must comply with the instructions provided in this section, follow local wiring practices, take the
environmental conditions into consideration, and refer to IEC60950-1 Table 3B.
1.6.1 Maximum Steady State AC And DC Currents Maximum steady state AC and DC currents
UPS
rating
(kVA)
Rated current (A) Busbar stud size
Input mains
current
1
2
(at full
load with battery
recharging)
Output current
at full
load
Battery
discharge
current at
EOD
Main input,
output, bypass
input cables
Battery cables
380V 400V 415V 380V 400V 415V Bolt
Torqu e
(N.m)
Bolt Torque (N.m)
200 330 316 302 303 290 278 630
M8
15
M8
15
150, 160 280 265 255 225 215 205 525
120 224 212 204 180 172 164 420
90
100
168 159 153 135 129 123 315
60 112 106 102 90 86 82 210
40 75 71 68 60 57 55 140
30 56 53 51 45 43 41 105 M6 4.8
30-B 56 53 51 45 43 41 105 M6 4.8
Note:
1. Input mains current for common rectifier and bypass AC input.