Section 5957 Installation Guide
Issue AM, March 26, 2014 Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B)
Page 56
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
TPL Fuses Lug Adapter Kits
Fuseholder Assembly
P/N 514403
TPL Fuse
Load Lug Adapter Plate
1.000"
3/8" Clearance Holes
Lug Adapter P/N 513701,
Kit P/N 520892
(see Notes 1, 2, 3)
Notes:
1. Maximum size of wire to be connected to a single lug position is 750 kcmil.
2. Maximum lug width is 1.937 inches.
3. Kit includes Load Lug Adapter Plate, plus 1/4" and 3/8" mtg. hardware.
4. Lug adapter accepts a maximum of (2) 750 kcmil or (4) 350 kcmil lugs.
5. Lug adapter accepts a maximum of (4) 750 kcmil lugs.
6. Lugs are not part of the kit, shown for illustration only.
7. Bay busbars are not part of the kit, shown for illustration only.
8. Two (2) kits shown for illustration of the kit installed on busbars with tops
even with each other and staggered.
Lug Adapter Kits
Power/Distribution Bays
2-Position
Lug Adapter Kit
P/N 529132
(see Notes 4, 6, 7, 8)
Lug Adapter Kits
Distribution Only Bays
3/8" Clearance Hole
1.000"
GMT-18/100A
Alarm Fuse
and GMT-X
Safety Fuse Cover