Section 5957 Installation Guide
Issue AM, March 26, 2014 Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B)
Page 78
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
AC Input Connections to Lists 1 and 11 Power/Distribution Bays (w/out PDSC)
(Ten AC Feeds)
PCU #1
PCU #2
PCU #3
PCU #4
PCU #5
PCU #6
PCU #7
PCU #9
PCU #10
Front View
PCU #1
A B C
PCU #2
A B C
PCU #3
A B C
PCU #7
A B C
PCU #8
A B C
PCU #9
A B C
PCU #10
A B C
PCU #6
A B C
PCU #5
A B C
PCU #4
A B C
480VAC (List A) or 208VAC (List B), 3 Phase, 60Hz
Separate Feed per PCU
PCUAC INPUT: 1/4-20 Studs on 5/8" Centers for Installation of Customer Provided Two-Hole Lugs
Frame Ground
(1/4-20 Studs
for Installation of
Customer Provided
One-Hole Lugs)
Recm. Torque
Using supplied
1/4" hardware,
84 in-lbs.
Cover Removed
in Illustration
Vue de la page 79