Vue de la page 12
High-Capacity Rotary Valves
Product Flier
PF51.3:Vee-Ball
May 2009
13
Valve Positioners
Fisher 3610J, 3610JP, and 3620JP Valve Positioners
The 3610J single-acting pneumatic, 3610JP
double-acting pneumatic, and 3620JP double-acting
elector-pneumatic valve positioners are accurate,
efficient positioners for use with 1051, 1052, 1061
actuators.
Approvals Available
Electrical Classification (Applies to the 3620JP)
Intrinsic Safety, Explosion proof, Type
n Dust-Ignition proof, DIV 2,
Intrinsic Safety, Explosion proof, Type
n, Non-incendive, Dust-Ignition proof,
Intrinsic Safety, Type n, Flameproof
(Gas Atmospheres Only),
Intrinsic Safety, Type n, Flameproof,
(Gas Atmospheres Only),
Intrinsic Safety, Flameproof
Hazardous Area Classifications
The 3610J and 3620J valve positioners comply
with the requirements of ATEX Group II Category
2 Gas and Dust
W8693-1/IL
Figure 13. Fisher 3610J Pneumatic Valve Positioner and
i2p-100 Electro-Pneumatic Transducer with 1052 Actuator
and V300 Valve
Table 9. Fisher 3610J and 3620J Positioner Specifications
Type Input Signal Supply Pressure
Operative
Temperature
Weight Connections
3610J and
3610JP
0.2 to 1.0 or
0.4 to 2.0 bar
3 to 15 or
6 to 30 psig
0.3 bar above the
actuator requirement
up to 10.3 bar
maximum
40 to 80C
2.5 kg
Pressure and Vent
Connections: 1/4 NPT
3620J and JP Conduit: 1/2
NPT
3620J and
3620JP
4 to 20 mA constant current with 30
VDC maximum compliance voltage;
equivalent circuit is 120 ohms
shunted by three 5.6 V zener diodes
0.3 bar above the
actuator requirement
up to 10.3 bar
maximum
40 to 80C
3.6 kg
Table 10. Fisher 3610J and 3620J Capacities and Housing
Type Supply Pressure, Bar
Supply Air Demand,
Nm
3
/h
Air Consumption, Nm
3
/h
Housing (3620J and
3620JP)
3610J and 3620J
1.4 13
3610J: 0.40 to 1.4 bar supply
3620J: 0.49 at 1.4 bar supply
IP 54 per IEC 529
classification
(weatherproof), NEMA 3;
vent should be on the
side or bottom for
weatherproof applications
2.4 17
3610JP and 3620JP
5.2 37
3610JP: 0.64 at 6.9 bar supply
3620JP: 0.93 at 6.9 bar supply
6.9 46
APPROVED
ATEX
IECEx
INMETRO