Type HSR
D103074X012
Instruction Manual
Form 5753
February 2014
www.fisherregulators.com
Type HSR Pressure Reducing Regulator for
Residential, Commercial or Industrial Applications
WARNING
!
Failure to follow these instructions or
to properly install and maintain this
equipment could result in an explosion
and/or  re causing property damage and
personal injury or death.
Fisher
®
regulators must be installed,
operated and maintained in accordance
with federal, state and local codes, rules
and regulations and Emerson Process
Management Regulator Technologies,
Inc. instructions.
If the regulator vents gas or a leak
develops in the system, service to the unit
may be required.
Failure to correct trouble could result in a
hazardous condition.
Call a gas service person to service the
unit. Only a quali ed person shall install
or service the regulator.
Introduction
Scope of the Manual
This manual provides instructions for the installation,
adjustment, maintenance and parts ordering
information for the Type HSR residential and/or
industrial/commercial pressure regulator.
Description
The Type HSR direct-operated, spring-loaded regulators
with internal relief provide economical pressure
reducing control in a variety of residential, commercial
and industrial applications. These regulators can be
used with natural, manufactured or lique ed petroleum
gases. In addition, the Type HSR regulator has
internal relief across the diaphragm to help minimize
overpressure. Any outlet pressure above the start-to-
discharge point of the nonadjustable relief valve spring
moves the diaphragm off the relief valve seat, allowing
excess pressure to bleed out through the screened
spring case vent.
Figure 1. Type HSR Pressure Reducing Regulator
TYPE HSR ANGLE BODY TYPE HSR STRAIGHT
P1524 P1275
Vue de la page 0
1 2 3 4 5 6 7 8

Résumé du contenu

Page 1 - Type HSR

Type HSRD103074X012Instruction ManualForm 5753February 2014www.fisherregulators.comType HSR Pressure Reducing Regulator for Residential, Commercial or

Page 2

Type HSR2ORIFICE SIZEWIDE-OPEN Cg FOR RELIEF SIZINGMAXIMUM OPERATING INLET PRESSURE TO OBTAIN GOOD REGULATING PERFORMANCEInch mmpsigbar1/83/161/43/81

Page 3

Type HSR3UPPER SPRINGCASESTEMVALVE DISKORIFICELEVERPUSHER POSTRELIEF VALVE SPRINGCONTROL (MAIN) SPRINGINLET PRESSUREOUTLET PRESSUREATMOSPHERIC PRESSUR

Page 4

Type HSR4TO APPLIANCEVENT LINEBASEMENTVENT ASSEMBLYDo not install the regulator in a location where there can be excessive water accumulation, such as

Page 5

Type HSR5Figure 4. 7-inch w.c. / 17 mbar Setpoint Relief Curves (with lever disconnected, no vent piping and 3/4 or 1-inch / 19 or 25 mm vent)Figure 5

Page 6

Type HSR6Type HSR regulators provide internal relief that limits the total outlet pressure build-up over setpoint. This internal relief may be adequat

Page 7

Type HSR7When ordering replacement parts, reference the key number of each needed part as found in the following parts list. If construction changes a

Page 8

Type HSR©Emerson Process Management Regulator Technologies, Inc., 2003, 2014; All Rights ReservedThe Emerson logo is a trademark and service mark of E