Emerson SR8 Fiche technique Page 14

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 20
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 13
Bulletin 71.4:SR8
14
Table 7. Steam Capacities (continued)
SPRING RANGE,
PSIG (bar)
SET
PRESSURE,
PSIG (bar)
CAPACITIES IN POUNDS PER HOUR (kg/h) SATURATED STEAM AT % BUILD-UP
Elastomer Diaphragm Metal Diaphragm
NPS 1-1/2 (DN 40)  NPS 1-1/2 (DN 40)
10% 20% 30% 40% 10% 20% 30% 40%
2 to 8
(0,14 to 0,55)
2 (0,14)
30 (14) 40 (18) 46 (21) 56 (25)
Not Available5 (0,34) 36 (16) 66 (30) 120 (54) 170 (77)
8 (0,55) 42 (19) 91 (41) 200 (91) 290 (132)
5 to 25
(0,34 to 1,7)
5 (0,34) 32 (15) 40 (18) 64 (29) 76 (35) 32 (15) 36 (16) 45 (20) 53 (24)
15 (1,0) 72 (33) 170 (77) 310 (141) 360 (163) 51 (23) 68 (31) 102 (46) 140 (64)
25 (1,7) 110 (50) 300 (136) 560 (254) 650 (295) 71 (32) 100 (45) 160 (73) 220 (100)
15 to 70
(1,0 to 4,8)
15 (1,0) 73 (33) 120 (54) 180 (82) 260 (118) 53 (24) 66 (30) 92 (42) 120 (54)
30 (2,1) 290 (132) 460 (209) 520 (236) 620 (281) 100 (45) 160 (73) 250 (114) 340 (154)
45 (3,1) 500 (227) 800 (363) 870 (395) 970 (440) 140 (64) 260 (118) 400 (182) 550 (250)
50 (3,4) 570 (259) 910 (413) 990 (449) 1090 (495) 160 (73) 290 (132) 450 (204) 620 (281)
60 (4,1) 720 (327) 1140 (518) 1220 (554) 1330 (604) 190 (86) 360 (163) 550 (250) 760 (345)
70 (4,8) 860 (390) 1350 (613) 1440 (654) 1540 (699) 220 (100) 430 (195) 660 (300) 910 (413)
25 to 90
(1,7 to 6,2)
35 (2,4) 123 (56) 220 (100) 330 (150) 450 (204) 71 (32) 100 (45) 130 (59) 180 (82)
50 (3,4) 310 (141) 610 (277) 740 (336) 870 (395) 130 (59) 210 (95) 310 (141) 430 (195)
75 (5,2) 630 (286) 1240 (563) 1430 (649) 1560 (708) 220 (100) 400 (182) 610 (277) 850 (386)
90 (6,2) 820 (372) 1630 (740) 1800 (817) 1920 (872) 280 (127) 520 (236) 780 (354) 1100 (499)
35 to 100
(2,4 to 6,9)
35 (2,4) 190 (86) 280 (127) 420 (191) 640 (291) 97 (44) 140 (64) 190 (86) 260 (118)
50 (3,4) 360 (163) 600 (272) 790 (359) 990 (449) 140 (64) 230 (104) 360 (163) 500 (227)
75 (5,2) 640 (291) 1130 (513) 1400 (636) 1580 (717) 220 (100) 380 (173) 630 (286) 910 (413)
100 (6,9) 910 (413) 1660 (754) 1980 (899) 2110 (958) 290 (132) 530 (241) 900 (409) 1310 (595)
75 to 125
(5,2 to 8,6)
75 (5,2) 710 (322) 1250 (568) 1480 (672) 1580 (717) 440 (200) 680 (309) 870 (395) 960 (436)
100 (6,9) 950 (431) 1770 (804) 1950 (885) 2020 (917) 610 (277) 860 (390) 1220 (554) 1530 (695)
125 (8,6) 1420 (645) 2210 (1003) 2400 (1090) 760 (345) 1140 (518) 1630 (740)
Shaded areas indicate conditions where maximum differential pressure for the spring range is exceeded.
SPRING RANGE,
PSIG (bar)
SET
PRESSURE,
PSIG (bar)
CAPACITIES IN POUNDS PER HOUR (kg/h) SATURATED STEAM AT % BUILD-UP
Elastomer Diaphragm Metal Diaphragm
NPS 2 (DN 50)  NPS 2 (DN 50)
10% 20% 30% 40% 10% 20% 30% 40%
10 to 25
(0,69 to 1,7)
10 (0,69) 280 (127) 400 (182) 640 (291) 860 (390) 210 (95) 300 (136) 390 (177) 490 (222)
15 (1,0) 500 (227) 950 (431) 1190 (540) 1240 (563) 330 (150) 440 (200) 570 (259) 720 (327)
25 (1,7) 970 (440) 1560 (708) 1650 (749) 1740 (790) 460 (209) 660 (300) 910 (413) 1140 (518)
15 to 50
(1,0 to 3,4)
15 (1,0) 440 (200) 660 (300) 950 (431) 1190 (540) 250 (114) 370 (168) 460 (209) 510 (232)
25 (1,7) 690 (313) 1240 (563) 1590 (722) 1730 (785) 410 (186) 590 (268) 820 (372) 1030 (468)
50 (3,4) 1800 (817) 2500 (1135) 2780 (1262) 2940 (1335) 780 (354) 1340 (608) 1880 (854) 2380 (1081)
25 to 60
(1,7 to 4,1)
25 (1,7) 630 (286) 1130 (513) 1640 (745) 1740 (790) 410 (186) 590 (268) 830 (377) 1060 (481)
50 (3,4) 1470 (667) 2600 (1180) 2800 (1271) 2970 (1348) 750 (341) 1250 (568) 1790 (813) 2290 (1040)
60 (4,1) 2490 (1130) 3680 (1671) 3940 (1789) 1230 (558) 2160 (981) 3030 (1376)
Shaded areas indicate conditions where maximum differential pressure for the spring range is exceeded.
SPRING
RANGE,
PSIG (bar)
SET
PRESSURE,
PSIG (bar)
CAPACITIES IN POUNDS PER HOUR (kg/h) SATURATED STEAM AT % BUILD-UP
Elastomer Diaphragm Metal Diaphragm
NPS 3 (DN 80) NPS 3 (DN 80)
10% 20% 30% 40% 10% 20% 30% 40%
10 to 25
(0,69 to 1,7)
10 (0,69) 400 (182) 560 (254) 820 (372) 1000 (454) 270 (123) 470 (213) 630 (286) 770 (350)
15 (1,0) 510 (232) 860 (390) 1190 (540) 1540 (699) 440 (200) 680 (309) 890 (404) 1080 (490)
25 (1,7) 930 (422) 1570 (713) 2210 (1003) 2410 (1094) 660 (300) 1040 (472) 1370 (622) 1700 (772)
15 to 50
(1,0 to 3,4)
15 (1,0) 390 (177) 620 (281) 940 (427) 1260 (572) 420 (191) 640 (291) 840 (381) 1020 (463)
25 (1,7) 630 (286) 1280 (581) 1950 (885) 2410 (1094) 550 (250) 980 (445) 1270 (577) 1620 (735)
50 (3,4) 1080 (490) 2410 (1094) 3800 (1725) 4100 (1861) 1240 (563) 2140 (972) 2800 (1271) 3430 (1557)
25 to 60
(1,7 to 4,1)
25 (1,7) 590 (268) 1130 (513) 1660 (754) 2190 (994) 550 (250) 930 (422) 1280 (581) 1580 (717)
50 (3,4) 1150 (522) 2390 (1085) 3710 (1684) 4100 (1861) 1150 (522) 1950 (885) 2660 (1208) 3270 (1485)
60 (4,1) 2950 (1339) 4520 (2052) 5460 (2479) 1840 (835) 3050 (1385) 4090 (1857)
Shaded areas indicate conditions where maximum differential pressure for the spring range is exceeded.
Table 7. Steam Capacities (continued)
Table 7. Steam Capacities (continued)
Vue de la page 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 20

Commentaires sur ces manuels

Pas de commentaire