
8
Thermal Expansion Valves
Emerson Climate Technologies
Large uctuations in superheat in the suction gas are
usually the result of trapped liquid at the remote bulb
location. Even on properly designed suction lines, it is
sometimes necessary to move the remote bulb a few
inches from the original location to improve TXV perfor-
mance.
On multi-circuit evaporators fed by one TXV, install
the remote bulb at a point where the suction gas has
had an opportunity to mix in the suction header. Tighten
clamps so that the remote bulb makes good contact with
the suction line. NEVER APPLY HEAT NEAR THE
REMOTE BULB LOCATION WITHOUT FIRST RE-
MOVING THE REMOTE BULB.
Hunting
“Hunting” of TXVs is dened as the alternate over-
feeding and starving of the refrigerant ow to the
evaporator. Hunting is characterized by extreme cyclic
changes in the superheat of the refrigerant gas leaving
the evaporator and the evaporator or suction pressure.
Hunting is a function of the evaporator design, length
and diameter of tubing in each circuit, load per circuit,
refrigerant velocity in each circuit, temperature differ-
ence (TD) under which the evaporator is operated, ar-
rangements of suction piping and application of the TXV
remote bulb. “Hunting” can be reduced or eliminated by
the correct rearrangement of the suction piping, reloca-
tion of the bulb and use of the recommended remote
bulb and power assembly charge for the TXV.
Operation at Reduced Capacity
The conventional TXV is a self-contained direct oper-
ated regulator which is inherently susceptible to hunting
because of its design and the design of the system to
which it is applied.
The ideal ow rate would require a TXV with perfect
dynamic balance, capable of instantaneous response
to any change in evaporation (anticipation) and with a
means of preventing the TXV from over shooting the
control point because of inertia (compensation). With
these features a TXV would be in phase with the system
demand at all times and hunting would not occur.
A conventional TXV does not have built in anticipating
or compensating factors. A time lag will exist between
demand and response, along with the tendency to over
shoot the control point. The conventional TXV may get
out of phase with the system and hunt. An example of
overshooting occurs when the load increases, causing
the superheat of the suction gas to increase. The time
interval between the instant the remote bulb senses the
increase and causes the TXV pin to move into opening
direction allows the superheat of the gas to increase still
further.
In response to the rising superheat during the time
lags, the TXV has moved further in the opening direc-
tion, overshooting the control point and allowing more
refrigerant to ow to the evaporator than can be boiled
off by load.
When the TXV nally responds to the over-feeding of
the evaporator coil, it closes and will tend to again over-
shoot the control point and remain overly throttled until
most of the liquid refrigerant has left the evaporator.
The ensuing time delay before the TXV moves in the
opening direction allows superheat of the suction gas
to again rise beyond the control point. This cycle, being
self-propagating, continues to repeat.
Experience has shown that a TXV is more likely to
hunt at low load conditions when the TXV pin is close to
the valve seat. This is because of an unbalance be-
tween the forces which operate the TXV.
Besides the three main forces that operate the TXV,
the pressure difference across the TXV port also acts
against the port area and depending on TXV construc-
tion, tends to force the TXV either open or closed.
When operating with the pin close to seat, the follow-
ing will occur:
With the TXV closed, there is liquid pressure on the
inlet side of the pin and evaporator pressure on the
outlet.
When the TXV starts to open allowing ow to take
place, the velocity through the TXV throat will cause a
point of lower pressure at the throat, raising the pressure
difference across the pin and seat.
This sudden rise in pressure differential while acting
on the port area will tend to force the TXV pin back into
the seat. When the TXV again opens, the same type of
action occurs and the pin bounces off the seat with a
rapid frequency. This phenomenon is more frequently
encountered with the larger conventional ported TXVs
as compared to balance ported TXVs as the force
caused by the pressure differential is magnied by the
larger port area.
Most TXVs, when properly selected and applied, will
overcome these factors and operate with virtually no
hunting over a fairly wide load range.
Conventional ported TXVs will perform well to some-
what below 50% of nominal capacity depending on
evaporator design, refrigerant piping, size and length of
evaporator, and rapid changes in loading.
Nothing will cause a TXV to hunt quicker than un-
equal feeding of the parallel circuits by a distributor or
unequal air loading across the evaporator circuits.
Commentaires sur ces manuels