Quick Start Guide00825-0100-4801, Rev MAMay 2015Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeterwith HART® Protocol48
May 201510Quick Start GuideFigure 7. Transmitter WiringA. RL ≥ 250 ΩB. Power supplyNoteInstallation of the transient protection terminal block does n
Quick Start Guide11May 20153. Replace the housing cover. It is recommended the cover be tightened until there is no gap between the cover and the hous
May 201512Quick Start GuideFigure 9. Remote Mount Display Wiring DiagramA. Remote mount displayB. Junction box housingC. 4-20 mANoteWire colors provi
Quick Start Guide13May 2015Quick connect wiring (if applicable)As standard, the 3051S Quick Connect arrives properly assembled to the sensor module an
May 201514Quick Start GuideFigure 11. Quick Connect Housing Pin-OutA. GroundB. No connectionNoteFor other wiring details, refer to pin-out drawing an
Quick Start Guide15May 2015Step 5: Verify configurationUse any HART-compliant master to communicate with and verify configuration of the 3051S. Field
May 201516Quick Start GuideTable 1. Traditional Interface - Device Revision 6 or 7 and DD Revision 7 Fast Key SequenceFunctionFast Key sequenceAlarm
Quick Start Guide17May 2015Upper Sensor Trim1, 2, 3, 3, 3Zero Trim1, 2, 3, 3, 1Table 2. Device Dashboard - Device Revision 7 and DD Revision 9 Fast K
May 201518Quick Start GuideStep 6: Trim the transmitterTransmitters are shipped fully calibrated per request or by the factory default of full scale (
Quick Start Guide19May 2015Product CertificationsRev 1.0European Directive InformationA copy of the EC Declaration of Conformity can be found at the e
May 20152Quick Start GuideNOTICEThis guide provides basic guidelines for Rosemount 3051S Transmitters (reference manual document number 00809-0100-480
May 201520Quick Start GuideNoteTransmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using general Division 2 wiring method
Quick Start Guide21May 2015EuropeE1 ATEX FlameproofCertificate: KEMA 00ATEX2143XStandards: EN 60079-0:2012, EN 60079-1: 2007, EN 60079-26:2007(3051SF
May 201522Quick Start Guide2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accord
Quick Start Guide23May 2015N1 ATEX Type nCertificate: BAS01ATEX3304XStandards: EN 60079-0: 2012, EN 60079-15: 2010Markings: II 3 G Ex nA IIC T5
May 201524Quick Start GuideI7 IECEx Intrinsic SafetyCertificate: IECEx BAS 04.0017XStandards: IEC 60079-0: 2011, IEC 60079-11: 2011Markings: Ex ia
Quick Start Guide25May 2015Special Conditions for Safe Use (X):1. If the apparatus is fitted with optional 90 V transient suppressor, it is not capabl
May 201526Quick Start Guide2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accord
Quick Start Guide27May 2015Special Conditions for Safe Use (X):1. For ambient temperature above 60 °C, cable wiring must have minimum isolation temper
May 201528Quick Start GuideSpecial Condition for Safe Use (X):1. The Model 3051S Transmitters fitted with transient protection are not capable of with
Quick Start Guide29May 20157. Cable entry, certified by NEPSI with type of protection Ex d IIC in accordance with GB3836.1-2000 and GB3836.2-2000, sho
Quick Start Guide3May 2015Step 1: Mount the transmitterLiquid flow applications1. Place taps to the side of the line.2. Mount beside or below the taps
May 201530Quick Start Guide3. Intrinsically safe parameters:4. The product should be used with Ex-certified associated apparatus to establish explosio
Quick Start Guide31May 20153. Cable glands, conduit or blanking plugs, certified by NEPSI with Ex e or Ex n protection type and IP66 degree of protect
May 201532Quick Start GuideEAC – Belarus, Kazakhstan, RussiaEM Technical Regulation Customs Union (EAC) FlameproofCertificate: RU C-US.GB05.B.00835Mar
Quick Start Guide33May 2015Additional CertificationsSBS American Bureau of Shipping (ABS) Type ApprovalCertificate: 00-HS145383-6-PDAIntended
May 201534Quick Start GuideFigure 16. Rosemount 3051S Declaration of Conformity4801_QIG_RevMA.fm Page 34 Wednesday, May 6, 2015 1:15 PM
Quick Start Guide35May 20154801_QIG_RevMA.fm Page 35 Wednesday, May 6, 2015 1:15 PM
May 201536Quick Start Guide4801_QIG_RevMA.fm Page 36 Wednesday, May 6, 2015 1:15 PM
Quick Start Guide37May 20154801_QIG_RevMA.fm Page 37 Wednesday, May 6, 2015 1:15 PM
May 201538Quick Start Guide4801_QIG_RevMA.fm Page 38 Wednesday, May 6, 2015 1:15 PM
Quick Start Guide39May 20154801_QIG_RevMA.fm Page 39 Wednesday, May 6, 2015 1:15 PM
May 20154Quick Start GuideUsing a mounting bracketIf the transmitter requires the use of a mounting bracket, use the images below for instructions on
Rosemount World HeadquartersEmerson Process Management 6021 Innovation BlvdShakopee, MN 55379, USA+1 800 999 9307 or +1 952 906 8888+1 952 949 7001 RF
Quick Start Guide5May 2015Bolting considerationsIf the transmitter installation requires assembly of the process flanges, manifolds, or flange adaptor
May 20156Quick Start Guide2. Finger-tighten the bolts.3. Torque the bolts to the initial torque value using a crossing pattern. See Figure 3 for initi
Quick Start Guide7May 2015O-rings with flange adaptorsIn-line gage transmitter orientationThe low side pressure port (atmospheric reference) on the in
May 20158Quick Start GuideStep 2: Consider housing rotationTo improve field access to wiring or to better view the optional LCD display:1. Loosen the
Quick Start Guide9May 2015Figure 6. Transmitter switch and jumper configurationA. Meter/adjustment moduleB. SecurityC. AlarmStep 4: Connect wiring an