SPECIFICATIONS
This 2U POD is intended for use with a UPS meeting all the following requirements:
UPS input cord is compatible with the rating and type of receptacle on the
2U POD labeled “CONNECT UPS LINE CORD HERE.”
UPS output receptacle is compatible with the 2U POD input power connector
labeled “UPS.”
Available utility receptacle is compatible with the 2U POD input power connector
labeled “UTILITY.”
Transfer Time (to and from maintenance bypass) < 6 milliseconds
Operating Ambient Temperature 32°F to 104°F (0°C to +40°C)
Storage Ambient Temperature -4°F to 140°F (-20°C to +60°C)
Dimensions W x D x H: in. (mm) 3.5 x 3.0 x 15.5 (88 x 77 x 394)
Weight: lbs (kg) 10 (4.5)
Length of input utility cord: ft (m) 10 (3.0)
Length of input cord going to UPS: ft (m) 6 (1.8)
Humidity 0 to 95% non-condensing
Agency/Standards UL 1778, c-UL, ISTA Procedure 1A