www.Fisher.com
INMETRO Hazardous Area Approvals for
Fisherr 646 Electro‐Pneumatic Transducer
This supplement provides INMETRO Hazardous Area Approval information for the 646 transducer electro-pneumatic
transducer. Use this in conjunction with information provided in the 646 instruction manual (D101351X012)
.
INMETRO—National Institute of Metrology, Quality and Technology. INMETRO approval is accepted in Brazil.
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring
requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may
override, the standard installation procedures. Refer to the instruction manual
for all other information regarding 646
transducers.
Note
This information supplements the nameplate markings affixed to the product.
Always refer to the nameplate itself to identify the appropriate certification.
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion,
and area re‐classification.
Certificate Number: IEx 14.0240
Standards Used for Certification
ABNT NBR IEC 60079-0:2013
ABNT NBR IEC 60079-1:2009
ABNT NBR IEC 60079-11:2013
ABNT NBR IEC 60079-15:2012
Intrinsically Safe
Ex ia IIC T5/T4 Ga
Tamb = -40_C to: +40_C for T5 ; +71_C for T4
Nominal Characteristics:
30 Vmax, 4-20 mA
Ui = 30 V ; Ii = 150 mA ; Pi = 1 W ; Ci = 0 nF ; Li = 0 mH