Connections and Configuration
Liebert
®
Liqui-tect
®
14
3.0 CONNECTIONS AND CONFIGURATION
Input and output connections to the Liebert
®
Liqui-tect
®
panel may be made in any order—it is not
necessary, for example, to make all input connections before making any output connections. Use
copper conductors only for all wiring.
CAUTION
Be sure that the power wiring is disconnected from the Liebert Liqui-tect panel before
connecting any wiring to this unit or changing input or output connections.
Table 4 Wiring specifications
Connection Supported Wire Type Maximum Wire Length Rating
Cable
Input
4-wire Liebert Connection Cable
(CONNECT10) - furnished with
Liebert Liqui-tect panel
Connection cable - 10 ft. (3m)
Leak detection cable - 5000 ft. (1524m)
N/A
Alarm
Output
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
18 AWG* @ 1A 200 ft. (60m)
24VAC @ 1A20 AWG @ 1A 100 ft. (30m)
22 AWG @ 1A 75 ft. (23m)
Analog
Output
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
750 ft. (225m)
4-20mA
Signal
Output
Communication
RS232
Null Modem Cable 50 ft. (15m) N/A
Communication
IGM422
Liebert
®
SiteScan
®
18-22 AWG Stranded & Shielded
22 AWG* (recommended)
Non Plenum - Belden 9461
Plenum - Belden 88761
1000 ft. (300m) N/A
24VAC Power
Connection
(TB7)
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 8770
Plenum - Belden 88770
150 ft. (45m) 24VAC @ 1A
* Recommended