ROC364 Instruction Manual
Rev 5/00 6-9
+ Positive Pulse Input (Sourced)
- Common
To wire a pulse input channel (shown in Figure Section: 6-8), connect the “+” and “-” field wires to
terminals “+” and “-” on the I/O Card pulse input channel. When the field device completes the circuit
between the “+” and “-” terminals, an LED indicator next to the terminal block lights to show activity,
and the optical circuitry is triggered, producing a signal to the ROC accumulator.
CAUTION
The Pulse Input Source channel is designed to operate only with non-powered
discrete devices such as “dry” relay contacts or isolated solid-state switches. Use of
the channel with powered devices may cause improper operation or damage.
ROC-POWERED
PULSE DEVICE
+
-
6.65K
A13 to A16
+T
+
-
DOC0310A-R32
PI
COM
Figure Section: 6-8. Pulse Input Wiring