Emerson NetSure 722 Bulk Output Power System Fiche technique Page 157

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 166
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 156
NetSure
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
147
3. Select Signal or Register for Input 1.
4. Enter either the register number or choose the equipment, signal type, and signal name. The format for entering a register is
R(x), where x is the number of the register.
5. Setup Input 2 in the same way as Input 1 if it’s not disabled.
6. Enter Param 1 and Param 2 if they are not disabled. The format for entering a parameter is P(x), where x is the value.
7. Select Signal or Register for Output.
8. Enter either the register number or choose the equipment, signal type, and signal name.
9. Click the ADD button in the bottom of the window.
10. Reboot the ACU+. See “Restore Defaults Sub-Menuon page 132.
Vue de la page 156
1 2 ... 152 153 154 155 156 157 158 159 160 161 162 ... 165 166

Commentaires sur ces manuels

Pas de commentaire