Specifications
40
8.0 SPECIFICATIONS
Table 16 OpenComms EM specifications
Power Requirements EM & EM PDU controller vEM-14 controller
NOTE
Input 120 VAC, 60 Hz 120 VAC, 60 Hz
If the equipment is used
in a manner not specified
by the manufacturer, the
protection provided by the
equipment may be
impaired.
Output 9 VDC, 500 mA, unregulated 9 VDC, 500 mA, unregulated
Dimensions
W x D x H, in. (mm)
4.75 x 2.5 x 1.625
(120.7 x 63.5 x 41.3)
17 x 5 x 1.75
(431.8 x 127 x 44.5mm)
Weight 7 oz. (198g) 2 lb. (0.9kg)
Mounting 0U, wall-mount or desktop
1U, wall-mount, rack-mount
or desktop
Ambient Operating
Environment, °F (°C)
32 to 158 (0 to 70)
10-95% RH non-condensing
32 to 158 (0 to 70)
10-95% RH non-condensing
Communications
Network Interface
RJ45 10BASE-T connector
HTTP (Web), E-mail, SNMP
RJ45 10BASE-T connector
HTTP (Web), E-mail, SNMP
Modem 9600 baud, Numeric 9600 baud, Numeric
Agency Listings FCC Class A, CE Mark FCC Class A, CE Mark
LEDs Power, Link, Modem, Sensor, Serial
Ports
Sensor Ports 24
Temperature, °F (°C),
with ranges:
-22 to 248 (-30 to 120) -22 to 248 (-30 to 120)
Humidity with ranges: 0 to 100% RH 0 to 100% RH
Contact closure Normally Open / Normally Closed
2 Serial Ports
(EM PDU & vEM-14
controllers)
MP Advanced Power Strips
10 Dry Contact
Inputs
(vEM-14 controllers)
Form C dry contacts