Modbus Communications
4
1.6 RTU Framing
The example below shows a typical query and response from a Liebert IntelliSlot 485 interface card.
The master device initiates a query asking Slave Device, with address 2, for holding registers
starting at holding register 40051 (offset 50) and including next 2 registers (3 total).
Table 4 Query sample
Slave
Address
Function
Code
Starting Register
Number of Registers
CRC16
CRC16
Hi Byte
Lo Byte
Hi Byte
Lo Byte
Hi Byte
Lo Byte
02
03
00
32
00
03
E5
FA
Table 5 Response sample
Slave
Address
Function
Code
Count:
Bytes of
Data
Register
CRC16
40051 Data
40052 Data
40053 Data
Hi Byte
Lo Byte
Hi
Lo
Hi
Lo
Hi
Lo
02
03
6
1
58
00
FA
00
54
1B
0D
Slave Device, with address 2, responds to Function Code 3 with 6 bytes of hexadecimal data and
ends with CRC16 checksum.
Register values:
40051 =
158(hex) =
344 (decimal)
40052 =
FA (hex) =
250 (decimal)
40053 =
54 (hex) =
84 (decimal)