Emerson Autochangeover Controllers AC8 Manuel d'utilisateur Page 21

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 149
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 20
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 21 of 149
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Setpoints (View)
Temperature Setpoint
40010
10
BS10_x
Temperature Tolerance
40011
11
BS11_x
Humidity Setpoint
40012
12
BS12_x
Humidity Tolerance
40013
13
BS13_x
Control Points (Set)
Unit On / Off
40349
349
BC01_x
Bit 0 on=unit off Bit 1 on=unit on
Temperature Setpoint
40350
350
BC02_x
Temperature Tolerance
40350
350
BC02_x
Multiply desired value by 1000
Humidity Setpoint
40351
351
BC03_x
Humidity Tolerance
40351
351
BC03_x
Multiply desired value by 1000
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Vue de la page 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 148 149

Commentaires sur ces manuels

Pas de commentaire